Operating Instructions
4.24.3 Trouble Reminder
READ STATUS
1=TROUBLE REMINDER
2=TIMERS
3=NAC
Read Status Screen #2
The screen indicates whether the Trouble Reminder feature is set to sound every 4 or 24 hours.
4.24.4 Timers
Pressing 2 while viewing Read Status Screen #2 will cause the following Timer screens to be displayed:
These screens will indicate the delay time, in seconds, for each of the first three and last possible delay options. The AC Loss Delay time
is displayed in hours.
4.24.5 NACs
Each NAC can be programmed individually with unique settings with the exception of Canadian Mode. When the Canadian Option is
selected in programming (see "Canadian Option" on page 79), all NAC settings are changed to that of NAC 1. While in Canadian Mode,
if any NAC is setting is changed, all other NACs will get those same settings. Pressing 3 while viewing Read Status Screen #2 will dis-
play the following screen:
The operator can press 1 to view the programmed options for NAC 1, 2 to view the programmed options for NAC 2, 3 to view the pro-
grammed options for NAC 3, or 4 to view the programmed options for NAC 4. The resulting screens will display the following informa-
tion:
Enable/Disable Status
Circuit Type (Bell, Strobe, etc.)
Silenceable/Nonsilenceable
Auto Silence Enable/Disable and time delay (in minutes)
Coding Selection (Temporal, Steady, etc.)
Zone Assignments
Silence Inhibit Enabled/Disabled
Synchronization Type (System Sensor, Wheelock, or Gentex)
MNS Override Enabled/Disabled
MNS Active Yes/No
4.24.6 Relays
READ STATUS
1=RELAYS
2=PROGRAM CHECK
3=HISTORY
Read Status Screen #3
The operator can view the programmed option for each relay by pressing the corresponding number key.
4.24.7 Program Check
Pressing 2 while viewing Read Status Screen #3 will cause a screen similar to the following to be displayed:
Pressing 1 while viewing Program Check screen #1 will display a screen which will indicate if any input zones have not been pro-
grammed to one of the Notification Appliance Circuits. Use the up and down arrow keys to view all NACs.
116
Pressing 1 while viewing Read Status Screen #2 will display the following screen:
TROUBLE REMINDER
TROUBLE REM
TIMERS
PAS DELAY
000
PRE SIGNAL
000
WATERFLOW
000
1=NAC 1
2=NAC 2
Pressing 1 while viewing Read Status Screen #3 will display the following screen:
1=RELAY 1
2=RELAY 2
3=RELAY 3
1=NACS NO INPUT
2=ZONES NO INPUT
3=ZONES NO OUTPUT
Program Check Screen #1
24HR
TIMERS
AC LOSS DELAY
CON MOD DLY
NAC
3=NAC 3
4=NAC 4
RELAY
PROGRAM CHECK
NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018