Close the battery cover
5
Dip Switch Positions (DS1)
1 2 3 4
1 2 3 4
1h
(default position)
Mode selection
1 2 3 4
7
Maintained operation
Non-maintained operation
8
9
Honeywell Life Safety AS, Po. Box 3514, N-3007 Drammen, Norway
Autonomy duration selection
The user can select one of the 3 available minimum autonomy
durations 1 hour, 3 hours and 8 hours. The selection must be
done while the luminaire is disconnected from AC and battery
1 2 3 4
supplies. The selection is achieved through Switches 2 & 3 of
3h
8h
DS1. Switch 1 is not used.
Technical label installation
One additional labels is included in the package, for 3 hours
duration (180). The installer must cover the default 1 hour (60)
printing. Please take notice of the orientation of the label.
Changing the operating mode
The control of maintained or non maintained operation of the
luminary is achieved through Switch 4 of DS1. For maintained
operation, switch number 4 must be in ON position. For non-
maintained operation, switch number 4 must be in OFF.
1 2 3 4
For accomplishing 8h autonomous light, an extra battery and
adaptor is required (Part No. 290BAT.9). Connect the two batteries
to the adaptor and then the adaptor's connector to the
corresponding connector on the PCB. One additional label is
included in the package, for 8 hours duration (480). The installer
must cover the default 1 hour (60) printing. Please take notice of
the orientation of the label.
Base the luminaire to the socket
Module placement
(elBus,Dali,Wireless,Potential free)
6
A test button for manual tests and
reset is located next to the
indications LEDs.