Technical description
Part no.:
Operation Voltage:
Maximum Power Consumption:
Battery (NiMH):
Battery Protection:
Min./Max. Charge Current:
Charge Voltage Range:
Charging Time:
Emergency Mode Duration:
Lumen output, normal:
Lumen output, emergency (1h/3h/8h):
Produced in accordance with:
Ambient Temperature Range:
Relative Humidity:
Degress of cover protection:
Technical lifetime (light source):
Weight:
Expected Battery Lifetime:
Controlgear classification in accordance with IEC 62034: with automatic test function
In case that the luminaire no longer meets its rated duration of operation, the battery must be replaced.
Battery Replacement:
Disconnect mains, carefully remove the luminaire from the ceiling or wall. Dismantle the luminaire.
Disconnect the battery and install a new one of the same type and charatecteristics.
Note: In case of battery replacement, this must be replaced with parts of the same type and characteristics.
The replacement must be performed by the manufacturer of a competent person.
Note: If the supply cable of the luminaire is damaged, it shall exclusively be replaced by a competent person
in order to avoid hazard.
Note: In case of mains power disconnection for a period of more that two months, the battery must be
disconnected.
Important notice when installing luminaires within the same area!!!
To avoid that luminaires perform their battery test at the same day, connect the battery packs with more
than 1,5 minutes inbetween.
The light source contained in this luminaire shall only be replaced by the manufacturer, or his agent,
or a similar qualified person.
NOTE! The light source is non-user replaceable.
At the end of their useful life the packaging, product
and batteries should be disposed of via a suitable
recycling centre. Do not dispose of with your normal
household waste. Do not burn.
Honeywell Life Safety AS, Po. Box 3514, N-3007 Drammen, Norway
ExitLED PRO M ST LED 230V w/pict 138h
220-240V AC, 50-60 Hz
4W / 4.25VA
3.6V / 1.7Ah
Overcharge protection / Deep discharge protection
50 / 170 mA
1h / 3h / 8h manually selected (default 1h)
220/185/75lm
EN 60598-1, EN 60598-2-22, EN 55015
EN 61547, EN 61000-3-2, EN 61000-3-3
> 100000 hours
138011
3.0 - 4.5 V
16 hours
220lm
o
5 to 40 C
Up to 95%
IP40
1000 gr
4 years
http://www.hls-nordic.com