Specifications - GE ATS125 Series Installation Manual

4-door dgp
Table of Contents

Advertisement

Specifications

General specifications
End of line resistor
Housing
PCB
Colour
Operating temperature
Humidity
IP protection grade
Mains power specifications
Mains input voltage
Current consumption
at 230 V~
Main board supply voltage
(J17)
Power supply specifications
Power supply voltage
Power supply current
Auxiliary power output
Battery power output
Battery type
Battery max. capacity
Main board consumption
Remaining current
Notes
Remaining current means all available current that can be used for the following: auxiliary power
(incl. switched), battery charge, lock power and local databus power. You can distribute the total
available current over the terminals as long as the maximum remaining current and fuse rating
for each output is respected.
ATS125x 4-Door DGP Installation Manual
ATS1251
ATS1252
(Other: 10 kΩ, 2%, 0.25 W; 2.2 kΩ, 2%, 0.25 W)
480 x 464 x 160 mm
230 V ~ ±10%, 50 Hz ±10%, 129 VA max.
13.8 ± 0.2 V
27.6 ± 0.2 V
4.0 A max.
1600 mA max.
@ 13.8 ± 0.2 V
@ 27.6 V
+ 1100 mA max.
@ 13.8 V
Note:
Maximum permanent current to power devices external to the
control equipment in the absence of alarm conditions.
13.8 ± 0.2 V
27.6 ± 0.2 V
1 x 26 Ah nom.
2 x 26 Ah nom.
3900 mA
1600 mA max.
@ 13.8 VDC
@ 27.6 VDC
+ 1000 mA max.
@ 13.8 VDC
ATS1253
Default: 4.7 kΩ, 2%, 0.25 W
445 x 315 x 90 mm
202 x 218 x 48 mm
Beige
−10 to +55°C
95% noncondensing
IP30
560 mA max.
30 VAC typical
13.8 ± 0.2 V
4.0 A max.
@ 13.8 ± 0.2 V
13.8 ± 0.2 V , 2 A max.
13.8 ± 0.2 V
Lead acid rechargeable
1 x 7.2 Ah nom.
or
1 x 18 Ah nom.
100 mA at 13.8 ± 0.2 V
3900 mA
@ 13.8 VDC
ATS1254
27.6 ± 0.2 V
1600 mA max.
@ 27.6 V
+ 1100 mA max.
@ 13.8 V
27.6 ± 0.2 V
2 x 7.2 Ah nom.
1600 mA max.
@ 27.6 VDC
+ 1000 mA max.
@ 13.8 VDC
19

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ats1251Ats1252Ats1253Ats1254