 Don't put tools or other conductive objects on the battery.
 It's prohibited to connect the anode of battery with the cathode of battery or connect
them reversely, which is to avoid fire or electric shock.
 Before connecting or disconnecting the battery terminals, disconnect charger first.
 The battery must be with the same type, model, and manufacturer.
 Battery should be kept away from fire source or all electrical equipments that may easily
cause spark avoid human injury.
 Don't open or destroy battery. The electrolyte in the battery includes some dangerous
objects, such as strong acid, which will be harmful to skin and eyes. If it is careless to
touch the electrolyte, clean it by a lot of water immediately and then check it in the
hospital.
 The waste battery should be disposed according to the local regulations.

ESD Protection

To prevent human electrostatic damaging sensitive components(such as circuit board), make
sure that to wear a anti-static wrist strap before touching sensitive components, and the other
end of wrist strap is well grounded.

Working Environment Requirements

 Don't install UPS where it would be exposed to direct sunlight, in rain or in moist
environments.
 Don't install UPS where it is with conductive metal dust or nearby heater.
 Generally, the working temperature is -5℃~+40℃ and the relative humidity is 0%RH~
95%RH that is with no condensation(The recommended working temperature is
20℃~25℃ and the recommended relative humidity is about 50%).
 Put UPS in the flat floor without vibration and the vertical gradient is less than 5°. Keep
good ventilation around UPS. The clearance between the rear or the side of UPS and
adjacent devices or wall should be at least 300mm~500mm. Poor ventilation will rise