Ups Parameters Setting - AEG UPS IST3 1-10kVA User Manual

Table of Contents

Advertisement

(1-10kVA) UPS IST3
User Manual
Inner power fault
Bypass fault

2.3.2 UPS Parameters Setting

Press and hold "SELECT" button for 5s to enter the set page. Then press "SELECT" button
to transfer the setting information, such as PAR/SGL mode (only available for parallel system),
ECO/INV mode or the inverting output voltage that is 208V/220V/230V/240V, and press "ON"
button to confirm the setting.
PAR mode (only available for parallel system)
"PAR" set page: When system works in the SGL mode and it has to set to PAR mode, in the
set page, three characters "PAR" flicker. If you confirm the selection, press and hold "ON"
button more than 1s to quit the set page, the setting is successful. If you aren't sure the
selection, it will quit the set page 20s later automatically. In the PAR mode, the LCD display
is as shown 0.
PAR mode
SGL mode (only available for parallel system)
"SGL" set page: When system works in the PAR mode and it has to set to SGL mode, in the
set page, three characters "SGL" flicker. If you confirm the selection, press and hold "ON"
button more than 1s to quit the set page, the setting is successful. If you aren't sure the
selection, it will quit the set page 20s later automatically.
23