SM 90 (see drawing 6c)
The following part has to be replaced in this component.
 Diaphragm 02
To replace these parts, the following steps are to be taken.
 Disconnect impulse line 21
 Unscrew screw connections 15
 Remove cover 01
 Remove diaphragm 02
 Remove diaphragm plates 05 and 07 with diaphragm 02 and nuts
 Remove nut 03
 Remove disk 05
 Replace the diaphragm 02, disk 05 and nut 03 use Loctite 243 (blue)
 Place the complete diaphragm assembly back
 Place cover 01
 Tighten screw connection 15 (even and diagonally)
 Connect impulse line.
Figure 6c: Pressure converter SM90