SBUS Wiring Distance
SBUS Wiring Distance
Calculate the total worst case current draw for all
modules on a single 4-conductor bus
Add the individual worst case currents for each module
Model Number
RA-2000 Fire Annunciator
5824 Serial/Parallel Printer Interface Module
5880 LED I/O Module
5865 LED Fire Annunciator
RPS-1000 Intelligent Power Supply
5496 Intelligent Power Supply
VIP-VCM/VIP-VCM with VIP-SW16
VIP-RM/VIP-RM with VIP-SW16
5815XL
VIP-50
Worst Case Draw
.120 amps
.150 amps
.040 amps
.250 amps
.200 amps
.010 amps
.010 amps
.010 amps
.125 amps/.200 amps
.125 amps/.200 amps
Max current
Max current
draw = 1 amp
per SBUS!
per SBUS!