C-TEC FF596 Installation Instructions Manual

Mfp repeater panel

Advertisement

Quick Links

MFP REPEATER PANEL
Installation Instructions
This document is written with the assumption that the reader is familiar with the functions and
installation details of the MFP range of fire panels. If this is not the case, then please familiarise yourself
with the MFP Instructions before proceeding any further.
MFP Repeater System Overview
The MFP Repeater system is designed to mimic the key functions of the MFP Main panel at other parts
of a building. These functions include:
Indicate zones in Fire (up to 32 zones, in multiples of eight)
Indicate a general system fault
Allow the user to Reset, Silence and Evacuate
Provide control outputs for Fire and Fault Conditions.
Up to eight MFP Repeater panels (Part No. FF596) may be connected to one MFP Main panel with power
and communication transmitted using 2 core network cable. The wiring may be run in any convenient
way that complies with the relevant Fire and Electrical Regulations for the site. The wiring may also be
spurred if required, see Figure 1 below:
Houses:
1 x Main Control PCB
1 x Repeater Transmitter PCB
MFP Main Panel
Figure 1 - Repeater System Overview
The Repeater system is implemented by installing a Repeater Transmitter PCB (Part No. FF596T) in the
MFP Main panel. This PCB handles the two wire communications network to the Repeaters.
Each Repeater consists of a Main Receiver PCB which connects to the 2 wire network. This PCB has the
Fault LEDs and controls and also incorporates the Fire Zone LEDs for the first eight zones. The Repeater
panel is expanded in multiples of eight by installing 8 Zone Extender PCBs (Part No. FF596R), up to a
maximum of 32 zones.
Installation Instructions
(Part No. FF596)
2-core network
2-core
network spur
Approved Document No. DFUR50010A Rev 2
Houses:
1 x Main Receiver PCB
n x 8 Zone Extender PCB
MFP Repeater Panel (FF596)
Houses:
1 x Main Receiver PCB
n x 8 Zone Extender PCB
MFP Repeater Panel (FF596)
1 of 8

Advertisement

loading

Summary of Contents for C-TEC FF596

  • Page 1 Provide control outputs for Fire and Fault Conditions. Up to eight MFP Repeater panels (Part No. FF596) may be connected to one MFP Main panel with power and communication transmitted using 2 core network cable. The wiring may be run in any convenient way that complies with the relevant Fire and Electrical Regulations for the site.
  • Page 2 FF596 MFP Repeater Panel The Repeater Transmitter PC (Part No. FF596T) PLK1 LOCAL PLK2 PL2 PL3 Repeater Transmitter PCB (FF596T) Figure 2 - Repeater Transmitter PCB The Repeater Transmitter PCB (shown in Figure 2 above) is mounted on, and takes its control signals and power from, the Main Control PCB which is mounted in the MFP Main panel.
  • Page 3 FF596 MFP Repeater Panel Installation Instructions Approved Document No. DFUR50010A Rev 2 • 3 of 8...
  • Page 4 FF596 MFP Repeater Panel Installing the Repeater Transmitter PC Note: Before installation, any short circuit or non-latching links should be fitted to the Main Control PCB’s first four zones, as alterations to these links requires removal of the Repeater Transmitter PCB.
  • Page 5 FF596 MFP Repeater Panel Repeater Panel Indicators and Controls Repeater Indicators The Main Receiver PCB, mounted in the MFP Repeater panel, has four system status LEDs and eight Fire Zone LEDs, which are detailed below. The General Fire LED (red) flashes when there is an unsilenced fire state on the system. When there is a silenced fire state on the system, this LED is lit steady.
  • Page 6 FF596 MFP Repeater Panel Repeater Panel Installation Fit the appropriate number of 8 Zone Extender PCBs in the MFP Repeater panel(s) as required for the system. These are installed by securing the PCBs to the lid with the spacers and nuts supplied and then connecting the supplied 6 way looms as shown in Figure 5 below.
  • Page 7: Testing The Installation

    FF596 MFP Repeater Panel Testing the Installation At the MFP Main panel, power up the system by connecting the Mains supply. The MFP Main panel will go through the Reset cycle and then settle after a few seconds with PSU and General Fault LEDs lit and the Fault beeper sounding intermittently.
  • Page 8 FF596 MFP Repeater Panel Repeaters with same address Symptoms: General Fault LED + Beeper on front of MFP Main panel, Repeater Transmitter PCB indicator LD3 lights periodically and indicator LD4 flashes once. Repeaters otherwise function correctly. Cause: Two or more Repeaters with SW4 set with same address.