Default I/O Connections - ABB ACS880+N5350 User Manual

Cooling tower drives
Table of Contents

Advertisement

7.7 Default I/O Connections

The default I/O connections of the 2-wire mode of the ACS880+N5350 primary control program are shown below.
o
t
3AXD50000011888
XP0W External power input
1
+24VI
24 VDC , 2 A
2
GND
XAI
Reference voltage and analog inputs
1
+VREF
10 VDC , R
2
-VREF
-10 VDC , R
3
AGND
Ground
4
AI1+
Speed reference
5
0(2)...10 V, R
AI1-
6
AI2+
By default not in use
7
AI2-
0(4)...20 mA, R
XAO
Analog outputs
1
A01
Motor speed rpm
2
AGND
0...20 mA, R
3
A02
Motor torque %
4
AGND
0...20 mA, R
XD2D
Drive-to-drive link
1
B
2
A
Drive-to-drive link
3
BGND
XR01, XR02, XR03 Relay outputs
1
NC
2
COM
3
NO
1
NC
2
COM
3
NO
1
NC
2
COM
3
NO
XD24
Digital interlock
1
DIIL
Digital Interlock, Thermostat, Ramp Stop
2
+24VD
+24 VDC 200 mA
3
DICOM
Digital input ground
4
+24VD
+24 VDC 200 mA
5
DIOGND
Digital input/output ground
XDIO
Digital input/outputs
1
DI01
Trickle current enable
2
DI02
De-Ice mode enable
XDI
Digital inputs
1
DI1
Stop (0) / Start (1)
2
DI2
By default, not in use
3
DI3
Acc/Dec �me set 1 (0) / set 2 (1)
4
DI4
Constant speed 2 (1 = On)
5
DI5
Reset Fault
6
DI6
External Event,
Safe torque off circuits must be closed for the drive
XSTO
to start. See Hardware manual of drive.
X12
Safety op�ons connec�on
X13
Control panel connec�on
X205
Memory unit connec�on
Figure 7-2
1...10 kohm
L
1...10 kohm
L
> 200 kohm
in
> 200 kohm
in
> 500 ohm
L
> 500 ohm
L
Ready
250 VAC / 30 VDC
2 A
Running
250 VAC / 30 VDC
2 A
Faulted (-1)
250 VAC / 30 VDC
2 A
Vibra�on Switch / External Trip
Wire sizes: 0.5 ... 2.5mm
(24...12AWG)
Tightening torques: 0.5 N·m (5lbf·in)
for both stranded and solid wiring.
Total load capacity of these
outputs is 4.8W (200mA / 24V)
minus the power taken by DIO1
and DIO2.
Must be Closed for the drive to