TECHNICAL DATA

2.1 Pressure Ranges

The transmitter is supplied in one of the standard (zero based) ranges or it can
be calibrated to any acceptable intermediate span. Refer to Table 1-1.
The transmitter label shows the factory calibrated range and the maximum
working pressure (MWP). The upper range limit (URL) = MWP.

2.2 Environment Data

Service
........................................................................................ Liquid, gas or vapour
Temperature
ambient ...................................................... - 40°C to +85°C (-40°F to +185°F)
(LCD Option)........................................ - 20°C to +70°C (-4°F to +158°F)
process..................................................... - 40°C to +120°C (-40°F to +248°F)
compensated.............................................. - 40°C to +85°C (-40°F to +185°F)
Humidity limit
......................................................................................................0 - 100% RH

2.3 Performance Data

Range adjustment
0
(URV - LRV): ≥ 1% URL
(mbar a)
LRV (or URV)
-1000
(mbar g)
Figure 2-1 shows the limits for range adjustment. For example:
Span: The minimum span available for a 2 bar device is 0.02 bar (100:1
down-ranging).
Zero offset: A 2 bar (MWP) gauge device can give 4 to 20 mA in the range
-1 bar to 2 bar. For example: If the span is 0.02 bar, 4 to 20 mA is available
anywhere in the range up to a maximum zero offset of 1.98 bar (calibrated
range = 1.98 to 2 bar).
Minimum span
Lower range value (LRV) = 4 mA pressure value
Upper range value (URV) = 20 mA pressure value
Figure 2-1: Range limits
RTX 1000H series user manual
2-1