1MRS756885 A
2.7
REM615
Application Manual
Table 5:
Predefined user categories
Username
VIEWER
OPERATOR
ENGINEER
ADMINISTRATOR
For user authorization for PCM600, see PCM600 documentation.
Communication
The IED supports a range of communication protocols including IEC 61850, IEC
®
60870-5-103, Modbus
available through these protocols.
The IEC 61850 communication implementation supports all monitoring and
control functions. Additionally, parameter setting and disturbance file records can
be accessed using the IEC 61850 protocol. Disturbance files are available to any
Ethernet-based application in the standard COMTRADE format. Further, the IED
can send and receive binary signals from other IEDs (so called horizontal
communication) using the IEC61850-8-1 GOOSE profile, where the highest
performance class with a total transmission time of 3 ms is supported. The IED
meets the GOOSE performance requirements for tripping applications in
distribution substations, as defined by the IEC 61850 standard. The IED can
simultaneously report events to five different clients on the station bus.
The IED can support five simultaneous clients. If PCM600 reserves one client
connection, only four client connections are left, for example, for IEC 61850 and
Modbus.
All communication connectors, except for the front port connector, are placed on
integrated optional communication modules. The IED can be connected to Ethernet-
User rights
Read only access
•
Selecting remote or local state with
•
Changing setting groups
•
Controlling
•
Clearing alarm and indication LEDs and textual indications
•
Changing settings
•
Clearing event list
•
Clearing disturbance records
•
Changing system settings such as IP address, serial baud rate
or disturbance recorder settings
•
Setting the IED to test mode
•
Selecting language
•
All listed above
•
Changing password
•
Factory default activation
and DNP3. Operational information and controls are
Section 2
REM615 overview
(only locally)
15