Environment
Operate the Programmable Controller in the following environment:
Supply voltage
Amplitude range
Temperature
Relative humidity
Vibration resistance
Shock resistance
Ambient air
Output module
Furnish the output module load power supply with a fuse for the protection of load short-circuits.
Ensure that the employed fuse is rated to match the load. If the employed fuse rating is higher
than specified, the printed circuit boards, case, and other items may burnout when the load is
shorted.
Table 1-1 Operating Environment
100 to 120 VAC, single-phase, 50/60 Hz±4%
85 to 132 VAC
At operation: 0 to 55°C; storage: -20 to 75°C
At operation: 30 to 90% RH; storage: 10 to 90% RH
0.6 G (1000 rpm)
10 G
3
Dust: 0.1 mg/m
or less (given that there is no corrosive gas)
S10mini
(output module)
Figure 1-2 Output Module Specifications
Fuse
Power
supply
Load
- 3 -
1 BEFORE USE