Pi Mode 1103 Primary Command Source Mode = 5 - ABB ACS260-04 Series User Manual

Component drive
Hide thumbs Also See for ACS260-04 Series:
Table of Contents

Advertisement

PI Mode 1103 PRIMARY COMMAND SOURCE MODE = 5

9902 Digital input 1 (T2)
0, 2,
Open: Stop (disable)
9..12
Closed: Run (enable)
Open: Stop (disable)
1
Closed: Run (enable)
Open: Stop (disable)
3, 7
Closed: Run (enable)
Normally Open (NO)
4
Momentary close to
run
Normally Open (NO)
5
Momentary close to
run
Normally Open (NO)
6
Momentary close to
run
Open: Stop (disable)
8
Closed: Run (enable)
PI Mode 1103=5, 9902=0
Remote closed loop PI feedback control with Local
Preset speed 1
PI Mode 1103=5, 9902=3
Digital input 2
Digital input 3
(T3)
(T4)
Open : PI control
PI feedback
Closed : Preset
analog input
speed 1
Open : PI control
PI feedback
Closed : Analog
analog input
input 1
External trip
Open : PI control
input :
Closed : Preset
Open: Trip,
speed 1
Closed: Run
Normally Closed
(NC)
PI Feedback
Momentary open
Analog Input
to stop
Normally Closed
Open: PI Control
(NC)
Closed: Preset
Momentary open
Speed 1
to stop
Normally Closed
Open: External
(NC)
Trip
Momentary open
Closed: Run
to stop
Open : Forward
run
PI feedback
Closed : Reverse
analog input
run
+24 Volt
Run (Enable)
PI / Preset Speed 1
PI Feedback
0 Volt
Application Macros 43
Analog input
(T6)
Analog input 1
Analog input 1
PI feedback
analog input
Analog Input 1
PI Feedback
Analog Input
PI Feedback
Analog Input
Analog input 1
PI Mode 1103=5, 9902=1
Remote closed loop PI feedback control with
Local Analog speed input
Comments
Analog Input 1 can
provide an adjustable
PI setpoint, by setting
Parameter 4010 = 1
Analog Input 1 can
provide an adjustable
PI setpoint, by setting
Parameter 4010 = 1
Connect external
motor thermistor PTC
type or similar to
digital input 3
Normally Open (NO)
Momentary close to
run
Normally Open (NO)
Momentary close to
run
Normally Open (NO)
Momentary close to
run
Analog Input 1 can
provide an adjustable
PI setpoint, by setting
Parameter 4010 = 1
+24 Volt
Run (Enable)
PI / Local (Hand)
PI Feedback
+10 Volt
Local (Hand) Ref
0 Volt

Advertisement

Table of Contents