Maintenance And Inspection; Periodic Check; Table 5-1 Maintenance And Inspection Items - Hitachi LQZ700 User Manual

Option sys sw
Table of Contents

Advertisement

5 MAINTENANCE

5.1 Maintenance and Inspection

5.1.1 Periodic check

To keep the module running in optimal condition, it requires checks. Make checks daily or
periodically (twice a year or more often).
Item
Module appearance
LED
Looseness of mounting
screws
Cable sheath condition
Dust sticking condition
Module replacement
Connector condition
Static electricity may damage the module. Before starting the work,
discharge all electrostatic charge from your body.
Before replacing the module, switch it off to avoid electrical shock hazards and
also to prevent it from being damaged or malfunctioning.

Table 5-1 Maintenance and Inspection Items

Check the module case for cracks, flaws and other defects. Such
defects can be a sign of breakage in the internal circuitry, causing the
system to malfunction.
Check to see if the module ERR LED has not glowed.
Check the module and communications cable mounting screws for
tightness. Give additional tightening to screws found loose. Loose
screws could cause the system to malfunction and lead to burnouts
after heating.
Check cable coverings for defects. A cable covering out of position
could cause the system to malfunction, incur electrical shock hazards,
or develop short circuits, resulting in burnouts.
Check to see if the module has not caught dust. If dust is noticed,
remove it with a vacuum cleaner or other apparatus. Dust could
cause short circuits in its internal circuitry, resulting in burnouts.
Replacing the module without switching it off could cause damage to
its hardware and software. Before replacing the module, switch it
off first.
Connectors might have their characteristics degraded to cause failures
if their contacts catch dust or foreign matter. Cover connectors out
of use with the protective cap supplied.
Point to check
DANGER
5-2

Advertisement