Outputs to control LEDs and
buzzer
Outputs
1
In the RTUA08 without jumpers the normality OUT status is NO
TK_S014 – Installation Manual
Power supply min : 12V – 15% = 10,2V
Voltage drop max : 10,2 – 10 = 0,2V
Cable resistance: Voltage drop / reader current max = 0,2 / 50mA = 4
Ohm
Cable length (m: Resistance / (cable resistance / 1000) / 2 =
= 4 / (52 /1000) / 2 = 38 mt
Type:
Open Collector
Number:
3 each Wiegand channel
Function:
Red LED, Green LED, Buzzer
Voltage:
0V...+14V max
Current:
80mA Max
Wire length connection: see installation manual – usually shielded
Type:
Power Open Collector (Drain)
Number:
2
Voltage:
10V...+14V (internal Power supply)
Voltage (absolute max): 10V...+30V (from external Power supply).
Current:
1,2A [5A / 2sec peak max – inductive
1
Normality
NO or NC via JP1 and JP2 Default = NO
Wire length connection: it depends on cable diameter, load current
sink and load min power supply – Not shielded
load]