Parameter
DC power supply
Weight
Dimensions (LxWxH)
Mounting
Operating temperature
Storage temperature
Storage relative humidity
®
LONWORKS
connection
Controlled Inputs
Wiegand Inputs
Power supply output for readers
22

TECHNICAL DATA

Value
12V +/-15% 70mA [nominal internal]
[up to 2.5A when driving power loads]
0,2 Kg
105x93x61 mm
Standard DIN/omega rail
-10 ÷ 55°C
-20 ÷ 70 °C
0 ÷ 90 % without condensation
Unshielded twisted-pair cable in free topology connection
FT3150 smart transceiver 78Kbps
Type: Controller on 5 states (open, close, cut, short, tamper)
Number: 2
Supply Voltage: 0V...+10V
Supply current: 0...3 mA
Voltage (absolute max): -24V...+40V
Wire length connection: total resistance < 10 Ohm – not shielded
Min detection time: 250 ms
Type Wiegand (normally high)
Number: 2
Voltage: 0V...+5V nominal (TTL) +14V Max
Timing BIT Pulse width: min 50us – max 10ms
BIT Interval time: min 500us – max 20ms
D0
D1
BIT Interval
Wire type and length connection: see the reader installation manual –
usually shielded
Voltage: 12V +/-15% (line voltage)
Current: 200mA Max (per channel)
Wire length connection: it depends on cable diameter, reader current
sink and reader min power supply– usually shielded – see reader
installation manual.
Example:
Cable 0,35mmq: Resistance 52 Ohm/Km
Reader:
V min 10 VDC
Current max 50mA
BIT Interval