10.5 Setting Sensor Parameters

Set sensor parameters based on site requirements.
Table 10-4 Sensor parameter settings
Main
Menu
Parameters
Settings
Issue 03 (2014-12-02)
Second-
Third-
Level
Level
Menu
Menu
If battery routes 1 and 2 are respectively connected to a battery string (each battery string consists of
four 12 V, 100 Ah batteries in series), set Battery1 Connected and Battery2 Connected to Yes and
others to No, and set Rated Capacity to 100 Ah.
If battery route 1 is connected to two battery strings in parallel (each battery string consists of four
12 V, 100 Ah batteries in series), set Battery1 Connected to Yes and others to No, and set Rated
Capacity to 200 Ah.
Second-
Third-
Level
Level
Menu
Menu
Power
Sensor
System
Config. Para.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Fourth-Level
Default
Menu
Value
Battery2
Yes
Connected
Rated Capacity
100 Ah
BLVD Enable
Yes
Fourth-Level Menu Default Value Setting
Water Sensor
Smoke Sensor
Ambient Temp.
Sensor
Ambient Humi.
Sensor
10 Commissioning
Setting Value
NOTE
If N battery strings are
connected, set Battery 1
Connected to Battery N
Connected to Yes, and set
the other parameters to
No.
Rated capacity of the
batteries in a battery
string.
NOTE
The batteries connected to
one circuit breaker or fuse
are called a battery string.
Yes, No
None
Set to Yes
or No as
None
required.
None
None
68