Ngi Board - Honeywell LC13-510 Manual

Dual node module service
Table of Contents

Advertisement

3.3.9 NGI Board

light does not go out.
SELF TST/ERR
• Ensure that NGIO board is properly installed.
• Replace NGI board.
• Replace NGIO board.
light goes out, but
SELF TST/ERR
one controller.
• Replace NGI board, and then the other NGI board in slot below it, if present (three-
board, redundant cable node).
• Replace K2LCN/K4LCN.
light goes out, but
SELF TST/ERR
all controllers.
• Replace K2LCN/K4LCN.
• Replace NGI board, then apply power. Repeat for other NGI board, if present. Retry
extracted boards.
light is lighted on controller, and
BUS TRAN ERR
the K2LCN/K4LCN.
• Replace NGI board, then apply power. Repeat for other NGI board, if present. Retry
extracted boards.
• Replace K2LCN/K4LCN.
light is lighted on a controller, and
BUS TRAN ERR
the K2LCN/K4LCN.
• Replace NGI board, then apply power. Repeat for other NGI board, if present. Retry
extracted boards.
• Replace K2LCN/K4LCN.
The TX (yellow) light indicates transmit activity. If this light is not on, troubleshoot the
Plant Information Network (PIN) cables and other interfaces.
There is a test jumper on the front of the NGI board (near the indicator lamps described
above). This jumper has two positions, TEST and NORMAL. This jumper should always be in
the NORMAL position when the network is operating. Placing this jumper in the TEST
position may disrupt operation of other nodes operating on the PIN.
Dual Node Module Service
(green) light does not light on
PASS MOD TEST
(green) light does not light on
PASS MOD TEST
DTAK TIME OUT
BGAK TIME OUT
CAUTION
3-13
3.3.9
is lighted on
is lighted on
9/95