Sensing Line Filter (Standard) - GE Baker Hughes 2900-40 Series Maintenance Manual

Pilot operated safety relief valve
Table of Contents

Advertisement

XXII. 2900-40 Series POSRV Options (Cont.)
requirements. In these cases, a preventive maintenance
program may be developed by monitoring the filters,
without taking the valve off line.
Figure 46: High Capacity Filter
ATTENTION!!
When servicing dual filters, procedures need to be in place
to perform a tag out / lock out of pilots under pressure if
they are in service.
© 2019 Baker Hughes, a GE company. All Rights Reserved.
E. Sensing Line Filter (Standard)
Figure 47: Dual Filter
Consolidated 2900 Pilot Operated Relief valves come
configured directly from the factory with specially designed
filters to ensure long term operation. These filters should be
maintained based on the service conditions and cleanliness
of the media the valve will be exposed to. Depending on
the amount of contamination expected to be introduced to
the valve, these filters need to be regularly inspected and
replaced to ensure proper flow through the valve is maintained.
Regular maintenance intervals should be established based
on inspection of the filter at the time of service. Heavy
accumulation at the filter is an indication that more frequent
maintenance is needed. In applications that call for exposure
to a significant amount of contaminants, our high capacity
filters should be installed that allow regular maintenance to
be performed easily. Please consult your factory authorized
representatives for details on how to obtain this configuration.
The high capacity filter configuration can be installed with
independent filters that allow the maintenance to be
performed while the valve remains in service.
Note: See page 74 for replacement filter parts information.
Consolidated 2900-40 Series POSRV Maintenance Manual | 57