english
Acontrol
PKE-6 /-10 / PKE-14
P-controller and speed controller for variable voltage 1 ~ fans
Operating Instructions
Software version: D1361A from Version 00
L-BAL-E042-GB 1002 Index 002
Part.-No. 00163314-GB

Advertisement

Table of Contents
loading

Summary of Contents for ZIEHL-ABEGG Acontrol PKE-6

  • Page 1 english Acontrol PKE-6 /-10 / PKE-14 P-controller and speed controller for variable voltage 1 ~ fans Operating Instructions Software version: D1361A from Version 00 L-BAL-E042-GB 1002 Index 002 Part.-No. 00163314-GB...
  • Page 2: Table Of Contents

    Operating Instructions Acontrol – model series PKE-6 /-10 / PKE-14 Content General notes ............. Structure of the operating instructions .
  • Page 3 Operating Instructions Acontrol – model series PKE-6 /-10 / PKE-14 7.5.1 For mode Speed controller 1.01 ........7.5.2 For operation as P-Controller 2.01...
  • Page 4: General Notes

    We do not accept any liability for possible errors or omissions in the information contained in data, illustrations or drawings provided. Ziehl-Abegg AG is not liable for damage due to misuse, incorrect use, improper use or as a consequence of unauthorized repairs or modications.
  • Page 5: Explanations Of Symbols

    Operating Instructions Acontrol – model series PKE-6 /-10 / PKE-14 Safety information Explanations of symbols Safety instructions are highlighted with warning triangles and are depicted according to the degree of hazard as follows. Attention! Hazardous area. Death or severe injury or signicant property damage can occur if the corresponding precautions are not taken! Danger owing to electric current Danger owing to electric current or voltage.
  • Page 6: Work On The Device

    There is no guarantee that parts from non-original sources are designed and manufactured in correspondence with load and safety requirements. Parts and optional equipment not supplied by Ziehl-Abegg are not approved by Ziehl-Abegg for use. Operator’s obligation of diligence •...
  • Page 7: Product Overview

    Operating Instructions Acontrol – model series PKE-6 /-10 / PKE-14 Product overview 3 Product overview Operational area The controller described is used for continuous speed adjustment on variable voltage 1~ motors used to drive ventilators or pumps. Maintenance The device must be checked for soiling and, if necessary, cleaned in periodic intervals. Transport •...
  • Page 8: Minimum Space Requirement

    Operating Instructions Acontrol – model series PKE-6 /-10 / PKE-14 Mounting Minimum space requirement In order to ensure sufcient ventilation of the device, clearance on all sides of at least 50 mm has to be maintained to the housing walls, switch cabinet doors, wiring ducts, etc. The same clearance applies to the installation of several devices next to each other.
  • Page 9: Electrical Installation

    Operating Instructions Acontrol – model series PKE-6 /-10 / PKE-14 Electrical installation 5 Electrical installation Safety precautions Danger owing to electric current • Work on electric components may only be carried out by trained electricians or by persons instructed in electricity under the supervision of an electrician in accordance with electrical engineering regulations.
  • Page 10: Motor Connection

    Operating Instructions Acontrol – model series PKE-6 /-10 / PKE-14 Electrical installation Motor connection The motor is connected at terminals U1 and U2. Several motors can be connected to the device. Attention The maximum total control current (specied for electronic voltage regulation) for all motors may not exceed the device’s rated current.
  • Page 11: Voltage Supply For External Devices (+24V, Gnd)

    Operating Instructions Acontrol – model series PKE-6 /-10 / PKE-14 Electrical installation Voltage supply for external devices (+24V, GND) There is an integrated power supply for external devices, e.g. a sensor. Terminal +24 V, output voltage tolerance +/- 20%. max. load current FTechnical data. It is not permissible to connect outputs of several devices to each other! In case of overload or short circuit (24 V –...
  • Page 12: Operating And Display Elements

    Operating Instructions Acontrol – model series PKE-6 /-10 / PKE-14 Operating and display elements 6 Operating and display elements n-min n-max / P-band °C 28.08.2008 v_pke_bedien_anzeige.VSD Potentiometer Function dependently on selected mode of operation • For Speed controller 1.01 without function. •...
  • Page 13: Base Setup

    Operating Instructions Acontrol – model series PKE-6 /-10 / PKE-14 Base setup 7 Base setup Programming of the desired function (Speed controller / P-Controller) • It is possible to use the device as a “Speed controller” or as a “P-controller”. Selection of the function must rst be made by setting the internal jumper “E1”...
  • Page 14: Function Of Dipswitches For Operation As Speed Controller (Dip Off )

    Operating Instructions Acontrol – model series PKE-6 /-10 / PKE-14 Base setup Function of dipswitches for operation as Speed controller 1.01 (DIP For operation as a speed controller, the output voltage is set manually by adjusting the built-in potentiometer, by an external potentiometer or external signal. The desired function is determined with dipswitch S1.
  • Page 15: For Operation As P-Controller

    Operating Instructions Acontrol – model series PKE-6 /-10 / PKE-14 Start-up 7.5.2 For operation as P-Controller 2.01 3.01 Without minimum speed cut OFF (DIP 2 = = factory setting) • 100 % Min. 35 % Max. = 100 % If no “n-min” is adjusted, the fan stops with reaching the desired value.
  • Page 16: Setting For Operation

    Operating Instructions Acontrol – model series PKE-6 /-10 / PKE-14 Setting for operation 9 Setting for operation Speed controller 1.01 9.1.1 Setting for operation as Speed controller Signal to: Setting via external signal or external potentiometer Setting range: Output voltage from approx. 0 - 100 % of connected line voltage or in range of settings “n-min”...
  • Page 17: Operation With Two Variable Output Voltages (Two Steps)

    Operating Instructions Acontrol – model series PKE-6 /-10 / PKE-14 Setting for operation 9.1.3 Operation with two variable output voltages (two steps) Switchover between two steps via external potential-free contact possible. • Step 1 (low speed). When there is no input signal connected to the input terminal “E1”, then the unit supplies the output voltage set by “n-min”.
  • Page 18: Example Temperature Control "Cooling Function" (Factory Setting)

    Operating Instructions Acontrol – model series PKE-6 /-10 / PKE-14 Setting for operation 9.2.2 Example Temperature control “Cooling function” (factory setting) • “Val > Set = n+” (DIP4 = • Temperature sensor type TF.. • Measuring range controller -26...+76 °C Settings: •...
  • Page 19: Pressure Control Condensers (P-Controller) 3.01

    Operating Instructions Acontrol – model series PKE-6 /-10 / PKE-14 Setting for operation Pressure control condensers (P-Controller) 3.01 9.3.1 Setting for operation as Pressure controller For control with active sensors (0 - 10 V, 4 - 20 mA) Setting range: 0 - 100 % ≙ measuring range of sensor 28.08.2008 v_set_pke.VSD n-max/ Pband...
  • Page 20: Setting With Refrigerant Medium Table

    Operating Instructions Acontrol – model series PKE-6 /-10 / PKE-14 Setting for operation 9.3.3 Setting with refrigerant medium table Information Calculation for relative pressure (differential measurement of pressure relative to ambient pressure). MBG-30I 0.00 1.50 3.00 4.50 6.00 7.50 9.00 10.50 12.00 13.50...
  • Page 21: Diagnostics / Faults

    Operating Instructions Acontrol – model series PKE-6 /-10 / PKE-14 Diagnostics / Faults 10 Diagnostics / Faults Operating conditions are indicated by the internal status LED with ashing code. Code Reaction of Controller Explanation Adjustment In the event of a mains interruption the unit switches “OFF”...
  • Page 22: Enclosure

    Operating Instructions Acontrol – model series PKE-6 /-10 / PKE-14 Enclosure 11 Enclosure 11.1 Technical data semiconductor fuse Max. heat dissi- Rated current Max. line fuse pation approx. Weight Type Part.-No. [Part.-No.] [kg] PKE-6 303614 FF20 A 6x32 mm 15 W (pack of 10 fuses: 349026) PKE-10...
  • Page 23: Connection Diagram

    Operating Instructions Acontrol – model series PKE-6 /-10 / PKE-14 Enclosure 11.2 Connection diagram Acontrol PKE-6 /10/14 °C Digital Analog Analog 24 V PE PE PE A1 GND E1 GND Eingang Input 0...10 V 2...10 V 0...20 mA 4...20 mA TF..(KTY)
  • Page 24 Operating Instructions Acontrol – model series PKE-6 /-10 / PKE-14 Enclosure 11.2.1 Connection diagram motor protection unit for motors with thermostats type S-ET10 • Full motor protection by switch-off when activating the attached thermostat switches. Reset after malfunction by key press. •...
  • Page 25: Dimensions [Mm]

    Operating Instructions Acontrol – model series PKE-6 /-10 / PKE-14 Enclosure 11.3 Dimensions [mm] PKE-6, PKE-10 PKE-14 Vor Öffnen des Deckels Gerät spannungsfrei schalten! Switch off the main supply before removing the cover! L-BAL-E042-GB 1002 Index 002 Part.-No. 00163314-GB 24/26...
  • Page 26: Index

    Operating Instructions Acontrol – model series PKE-6 /-10 / PKE-14 11.4 Index basic speed control cable external potentiometer external signal heat dissipation Input resistance line fuse mains is connected mains voltage maximum control current MBG-30I Minimum space requirement Minimum speed cut off Mode motor feed cable motor noise...
  • Page 27: Manufacturer Reference

    Manufacturer reference Our products are manufactured in accordance with the relevant international regulations. If you have any questions concerning the use of our products or plan special uses, please contact: Ziehl-Abegg AG Heinz-Ziehl-Straße 74653 Künzelsau Telephone: +49 (0) 7940 16-0 Telefax: +49 (0) 7940 16-504 info@ziehl-abegg.de...