english Acontrol PSET6 / PSET10 Speed controller for variable voltage 1~ fans Operating Instructions Keep for reference! L-BAL-E141-GB 1925 Index 004 Part.-No.
We do not accept any liability for possible errors or omissions in the information con- tained in data, illustrations or drawings provided. ZIEHL-ABEGG SE is not liable for damage due to misuse, incorrect use, improper use or as a consequence of unauthorized repairs or modifications.
Operating Instructions Acontrol PSET6 / PSET10 Safety instructions 2 Safety instructions This chapter contains instructions to prevent personal injury and property damage. These instructions do not lay claim to completeness. In case of questions and problems, please consult our company technicians.
Operating Instructions Acontrol PSET6 / PSET10 Safety instructions Information In the case of a malfunction or a failure of the equipment check all functions with alarms in order to prevent injury to persons or property. Note possibility of back-up operation. If...
ZIEHL-ABEGG.These parts were specifically designed for the device. There is no guarantee that parts from non-original sources are designed and manufactured in correspondence with load and safety requirements. Parts and optional equipment not supplied by ZIEHL-ABEGG are not approved by ZIEHL-ABEGG for use. 2.8 Operator’s obligation of diligence •...
Operating Instructions Acontrol PSET6 / PSET10 Product overview • The assembly instructions and/or operating instructions are always readily available at the location where the device is being used, are complete and are in legible condition. • These persons are regularly instructed in all applicable questions regarding occupa-...
Operating Instructions Acontrol PSET6 / PSET10 Mounting 4 Mounting 4.1 General notes Attention! The following points must be complied with during the mechanical installation to avoid causing a defect in the device due to assembly errors or environmental influences: •...
Operating Instructions Acontrol PSET6 / PSET10 Electrical installation 4.3 Outdoor installation Outdoor installation is possible up to -20 °C when the controller supply is not switched off. Installation must be protected from the effects of weather as much as possible, including protection from direct sunlight! 4.4 Installation location for agriculture...
Operating Instructions Acontrol PSET6 / PSET10 Electrical installation housing parts in metal terminal space covers and housing casings. Commissioning is only permissible after these screws have been properly attached! • The device owner is responsible for the EMC of the entire plant according to the locally applicable standards.
Operating Instructions Acontrol PSET6 / PSET10 Electrical installation 5.4 Motor connection The motor is connected at terminals U1 and U2. Several motors can be connected to the device. Attention! The maximum total control current (specified for electronic voltage regulation) for all motors may not exceed the device’s rated current.
Operating Instructions Acontrol PSET6 / PSET10 Electrical installation 5.6 Analog input (0 - 10 V, 2 - 10 V / 10 - 0 V, 10 - 2 V) The device has an analog input for setting fan speed. Terminals “E1” / “GND” (Analog In 1).
Operating Instructions Acontrol PSET6 / PSET10 Electrical installation 5.9 Enable, Device ON / OFF (Digital In 1 = D1) Electronic disconnection and Reset after motor fault via floating contact at termi- nals “D1” - “D1” • Device “ON” for closed contact.
Operating Instructions Acontrol PSET6 / PSET10 Base setup 6 Base setup 6.1 Internal Setting Attention! The controller housing cover may only be removed when the power line has been switched off! It is generally forbidden to carry out work on electrical live parts. Protection class of the device when open is IP 00! It is possible to touch hazardous voltages directly.
Operating Instructions Acontrol PSET6 / PSET10 Base setup 6.2 Dipswitch functions Position factory setting for all dipswitches = Function no selection RPM controller prohibited Setting of output voltage by exter- Signal source of control prohibited nal signal to “E1” Type of Signal...
Operating Instructions Acontrol PSET6 / PSET10 Base setup 6.4 Minimum speed cut off DIP 5 If no “n-min” is adjusted,output voltage goes continuously with reduction of the regulating variable down to “0” (cutoff below approx. 2 % regulating variable). Without minimum speed cut OFF (DIP 5 = = factory setting) •...
Operating Instructions Acontrol PSET6 / PSET10 Diagnostics / Faults energized no enable Switch OFF by external contact Terminals 12 - 14 Terminals “D1” - “D1” (Digital In 1) digital input). bridged not bridged. The unit cuts out and does not...
Operating Instructions Acontrol PSET6 / PSET10 Enclosure 9.1.1 Performance reduction during elevated ambient temperatures The maximum permissible temperature for the rated current at rated voltage is specified as rated temperature. Since the dissipation of the power loss (heat development) in the device is decisively dependent on the ambient temperature, the max.
Operating Instructions Acontrol PSET6 / PSET10 Enclosure 9.2 Connection diagram ...6 F1=M10 A / ...10 F1=FF20 A PSET6/10 Kontaktbelastung Contact rating max. AC 250 V 5 A Digital Analog Analog In 1 Out 1 In 1 A1 GND E1 GND...
Operating Instructions Acontrol PSET6 / PSET10 Enclosure 9.4 Manufacturer reference Our products are manufactured in accordance with the relevant international regulations. If you have any questions concerning the use of our products or plan special uses, please contact: ZIEHL-ABEGG SE Heinz-Ziehl-Straße...