Download Print this page

Honeywell WEB-O3022H Product Data

Ciper expansion i/o modules
Hide thumbs Also See for WEB-O3022H:

Advertisement

Quick Links

CIPer EXPIO Modules
© Honeywell
APPLICATION
The WEB-O3022H and WEB-O9056H are Expansion
I/O modules that are exclusively utilized with the CIPer
Model 30 Controller (either WEB-C3036EPVBNH or
WEB-C3036EPUBNH).
They can be directly connected to the CIPer Model 30
Controller or remotely mounted up to 100' away.
Multiple Expansion I/O Modules can be connected to a
single CIPer Model 30 Controller. You can mix the small
WEB-O3022H and the large WEB-CO9056H in any
combination to meet specific project I/O requirements.
The CIPer Model 30 Expansion I/O modules feature
removable terminal blocks, Hand-Off-Auto switches and
indicator LEDs and can be powered by the CIPer Model
30 Controller.
Features
• Plug-and-play functionality for each installation and
maintenance.
• All wiring connections are made to removable terminal
blocks to simplify device installation and replacement.
• Wide range of sensors supported sensors like 20KNTC,
PT1000 and other resistive sensors.
• Multiple Expansion I/O capability support and 300
additional points. Refer to CIPer Model 30 technical
documentation and SRB for more details.
• 16-bit A/D conversion resolution for accurate
measurement.
• Indication LEDs for all Digital and Analog Outputs (DO
& AO).
• HOA (Hand-Off-Auto) switches on DOs and AOs. HOA
are configurable and can be monitored.
• Compact size for small installation housings.
• Field configurable and programmable for control, input,
and output functions using the Niagara Framework®
based CIPer Model 30 programming tool.
PRODUCT DATA
31-00239EFS-01

Advertisement

loading

Summary of Contents for Honeywell WEB-O3022H

  • Page 1 Multiple Expansion I/O Modules can be connected to a single CIPer Model 30 Controller. You can mix the small WEB-O3022H and the large WEB-CO9056H in any combination to meet specific project I/O requirements. The CIPer Model 30 Expansion I/O modules feature...
  • Page 2 The WEB-O9056H module is a large expansion module which adds 20 additional I/O points, and the WEB-O3022H module is a small expansion module which adds 7 additional I/O points. Multiple expansion I/O modules can be added to a controller. Both I/O modules use the side-mounted terminal port to connect with the CIPer Model 30 Controller and additional I/O modules.
  • Page 3 35 VA maximum for I/O module without any -40° F to 250° F load. Outdoor Air C7041F (-40° C to 121° C) Temperature PT1000 WEB-O3022H: -40° F to 199° F (IEC751 87VA maximum for I/O module with all (-40° C to 93° C) 3850) oads. connected l...
  • Page 4 When mounting on DIN rail, the locking clip present fixed wiring. on both I/O modules ensures accurate alignment of The WEB-O9056H and WEB-O3022H are suitable for connectors between all modules. mounting in fuse boxes conforming with standard DIN43880 and having a slot height of max. 1.77 inches The controller can also be screw-mounted on a panel (45 mm).

This manual is also suitable for:

Web-o9056h