6.22

Quick Stop clockwise

The action "Quick Stop CW" results in the following behavior:
● The motor is switched off with pending signal "Motor CW" without group fault
● The motor is not switched off with pending signal "Motor CCW"
● "Quick Stop CW" takes priority over "Motor CW"
● The input action responds to the active edge of the input signal, which means
deactivation is possible when the static input signal "Quick Stop" is present.
● The input trigger is reset through cancelation of the control commands "Motor CW" or
"Disable quick stop" (in the process image). This applies only in the case of control via
manual local mode or in the case of a retentive Quick Stop signal.
Motor starter (3RK1308‑0**00‑0CP0)
Equipment Manual, 11/2019, A5E34821005002A/RS-AC/003
Functions
6.22 Quick Stop clockwise
123