Haier AV10IMWEWA Design, Installation & Maintenance Instruction page 30

Water-cooled
Table of Contents

Advertisement

AV26IMWEWA
1.00
0.95
0.90
0.85
0.80
0
20
40
60
pipe length of single way ( m )
AV30IMWEWA
1.00
0.95
0.90
0.85
0.80
0
20
40
60
pipe length of single way ( m )
AV34IMWEWA
1.00
0.95
0.90
0.85
0.80
0
20
40
60
pipe length of single way ( m )
Note:
1.The refrigerant pipe should be thickened when the single way length is over 90m.
2.When in cooling mode, outdoor is lower than indoor; or when in heating mode, outdoor is higher than indoor, the
compensation factor should be decreased the below value from the above figure.
Verti height drop between indoor
and outdoor
Adjustment factor
liquid pipe : Φ 19.05
gas pipe : Φ
liquid pipe :φ19.05
gas pipe :φ31.8
80
100
120
140
160
180
liquid pipe : Φ 19.05
gas pipe : Φ
liquid pipe :φ19.05
gas pipe :φ31.8
80
100
120
140
160
liquid pipe : Φ 19.05
gas pipe : Φ
liquid pipe :φ19.05
gas pipe :φ31.8
80
100
120
140
160
180
Height drop between indoor and outdoor adjustment factor
5m
10m
0.003
0.006
1.00
0.95
0.90
0.85
0.80
0
1.00
0.95
0.90
0.85
0.80
0
1.00
0.95
0.90
0.85
0.80
0
15m
20m
25m
0.009
0.012
0.015
29
AV28IMWEWA
liquid pipe :φ19.05
gas pipe :φ31.8
20
40
60
80
100
120
pipe length of single way ( m )
AV32IMWEWA
liquid pipe :φ19.05
gas pipe :φ31.8
20
40
60
80
100
120
pipe length of single way ( m )
AV36IMWEWA
liquid pipe :φ19.05
gas pipe :φ38.1
20
40
60
80
100
120
pipe length of single way ( m )
30m
35m
40m
0.018
0.021
0.024
liquid pipe : Φ 19.05
gas pipe : Φ
140
160
180
liquid pipe : Φ 19.05
gas pipe : Φ
140
160
180
liquid pipe : Φ 22.22
gas pipe : Φ
140
160
180
45m
50m
0.027
0.03