Haier AV10IMWEWA Design, Installation & Maintenance Instruction page 250

Water-cooled
Table of Contents

Advertisement

Indication
LD indication
on wired
on master
controller
unit
(hex)
21
15
22-0
16
22-1
16
23-0
17
23-1
17
23-2
17
24-0
18
24-1
18
25-0
19
25-1
19
Failure code definition
Ambient temp. sensor Tao
failure
Suction temp. sensor Tsi
failure
Suction temp. sensor Tsacc
failure
Discharging sensor Tdi failure
Discharging sensor Td1
failure
Outdoor gas pipe temp.
sensor Tdp/Tsuc failure
Oil temp. sensor Toilp failure
Oil temp. sensor Toili failure
Inlet temp. of heat exchanger
toci1 failure
Two1 water outlet 1 temp.
failure of water heat
exchanger
Failure description
AD value is detected below 11(open circuit) or above
1012 (short circuit) for 60 secs.
AD value is detected below 11(open circuit) or above
1012 (short circuit) for 60 secs. Cooling mode operate
without handling this abnormal sensor.
AD value is detected below 11(open circuit) or above
1012 (short circuit) for 60 secs. If tao≤0℃ , no detect of
the open circuit (ad value is blow 11).
AD value is below 11(open circuit) or above 1012(short
circuit), alarm. If Tao<0℃ , no open circuit failure alarm;
if Tao>=0℃ and ET>=0℃ , no open circuit failure alarm
in 5 minutes
AD value is below 11(open circuit) or above 1012(short
circuit), alarm. If Tao<0℃ or not in the normal running
condition, no open circuit failure alarm;
AD value is below 11(open circuit) or above 1012(short
circuit), alarm. No handling of this abnormal sensor when
cooling mode is operating.
249
Remarks
Resumable
Resumable
Resumable
Resumable
Resumable