(3) Installation place selection
Air-conditioner can't be
installed in the place with
inflammable gas. Or it will
cause fire hazard.
The unit should be installed at
the place where the cold/hot
air or
noise will not interfere the
neighbours.
Note:
1. Do not install the unit at the place where the flammable gas will leak.
2. Install the unit at the strong enough place.
3. Install the unit at the flat place.
4. After opening the electric box cover for maintenance, please fix the cover with screw firmly.
(4) Transportation
• During transportation, please don't unwrap the packaging, and move the unit to the
installation location as closely as possible.
• Don't hang the unit only at two points. When hanging the unit, don't sit on the unit.
The unit should be upright.
• When removing the unit with the forklift, put the fork into the special hole at the
bottom of the unit. When being hanged, the rope should be 4 pieces of steel cable
with over 6mm diameter.
• Put the cushion at the contact section between steel cable and the unit against the
distortion or damage.
Note:
When multiple modules are installed, the outdoor unit should be ranked as per the capacity, the larger capacity is
closer to the main pipe of gather pipe.
The unit should be installed at the
place with good ventilation. No
obstacle at the air inlet/outlet. And
no strong wind blows the unit.
The installation space refers to the
latter info.
• The place where the water can
flow fluently.
• The place where no other heat
source will affect the unit.
• Pay attention to the snow
against clogging the outdoor
unit.
• During installation, install the
anti-vibration rubber between
the unit and the bracket.
201
The unit should be installed at the strong
enough place. Or it will cause vibration
and noise.
• It is better not install the unit at the
below places, or it will cause damage.
• The place where there is corrosive
gas (spa area, etc).
• The place blowing salty air (seaside,
etc).
• The place existing strong coal smoke.
• The place with high humidity.
• The place where there is device
emitting Hertzian waves.
• The place where voltage changes
greatly.
Steel cable
Cushion
Bottom plate
Steel cable