Download Print this page

Honeywell XPO Series Manual page 12

Low temperature burner for use with clean fuel gases

Advertisement

VIII. TROUBLE SHOOTING 故障檢修
 
SYMPTOM 
 
故障現象
Pilot fails to light.  Burner 
locks out at pilot. 
 
點火失敗,燃燒器在點火時報
警。
Pilot fails to light.  Burner 
locks out at pilot. 
 
點小火失敗,燃燒器在點小火 時
報警。
Pilot fails to light.  Burner 
locks out at pilot. 
 
點火失敗,燃燒器在點小火時 報
警。
Pilot lights but extinguishes. 
Burner locks out at main 
flame. 
 
點著火後熄滅,燃燒器在主火 焰
處報警。
 
POSSIBLE CAUSE 
 
故障原因
a) No spark 
沒有火花
 
b) HT lead loose 
高壓線脫落
 
c) Spark gap incorrect 
火花塞間隙不正確
 
d) Transformer failed 
點火變壓器燒壞
a) No gas 
沒有燃氣
 
b) Too much gas 
燃氣過多
 
c) Pilot valve not open 
小火閥未打開
a) UV Scanner/Flame Rod 
not detecting flame 
UV 探頭/火焰棒探測不到火
 
b) Bad ground 
接地回路斷開
a)    Main valves not open 
主閥未打開
12
REMEDY 
 
補救措施
a) Tighten lead ends 
擰緊線接頭
 
b) Adjust spark gap 
調節火花塞間隙
 
c) Replace transformer 
更換變壓器
a) Restore gas supply 
恢復燃氣供應
 
b) Adjust gas pilot rate 
調節燃氣比率
 
c) Change valve 
替換閥門
 
d) Clear open circuit 
修復斷路的線路
Reposition UV 
a) 
Scanner/Flame Rod 
重新放置 UV 探頭/火焰棒
 
b)    Repair ground 
修理接地線路
a)    Restore main valve 
operation 
使主閥恢復運行
08092018

Advertisement

loading