Samsung AN026JSKLKN Series Installation Manual page 16

Erv, energy recovery ventilator
Hide thumbs Also See for AN026JSKLKN Series:
Table of Contents

Advertisement

Electric wiring
5 . Wrap it with the insulation tape twice or more and position your contraction tube in the middle of the insulation tape .
a total of three or more layers of insulation is required .
f Method 1
f
Insulation tape
40 mm
6 . apply heat to the contraction tube to contract it .
Contraction tube
7 . after tube contraction work is completed, wrap it with the insulation tape to finish .
• Make sure that the connection parts are not exposed to outside .
• Be sure to use insulation tape and a contraction tube made of approved reinforced insulating materials that have
CAUtIoN
the same level of withstand voltage with the power cable . (Comply with the local regulations on extensions . )
Insulation tape
• In case of extending the electric wire, please DO nOT use a round-shaped Pressing socket .
- Incomplete wire connections can cause electric shock or a fire .
WARNING
f Method 2
f
Insulation tape
35 mm