Samsung AN026JSKLKN Series Installation Manual

Samsung AN026JSKLKN Series Installation Manual

Erv, energy recovery ventilator
Hide thumbs Also See for AN026JSKLKN Series:

Advertisement

ERV(Energy Recovery Ventilator)
EN ES FR IT PT
DE
installation manual
imagine
the possibilities
Thank you for purchasing this Samsung product.
NL
DB68-05252A-02
AN026JSKLKN Series
AN035JSKLKN Series
AN050JSKLKN Series
AN080JSKLKN Series
AN100JSKLKN Series

Advertisement

Table of Contents
loading

Summary of Contents for Samsung AN026JSKLKN Series

  • Page 1 AN026JSKLKN Series AN035JSKLKN Series AN050JSKLKN Series AN080JSKLKN Series AN100JSKLKN Series ERV(Energy Recovery Ventilator) installation manual imagine the possibilities Thank you for purchasing this Samsung product. EN ES FR IT PT DB68-05252A-02...
  • Page 2: Table Of Contents

    Contents Before Installation Safety precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Space requirement .
  • Page 3: Safety Precautions

    Safety precautions Keep this installation manual together with the user’s manual in a handy place so that you can find it whenever you need to see it after reading this manual thoroughly . ❇ ❇ Make sure to read the following safety precautions carefully before installation . ❇...
  • Page 4 Safety precautions CAUtIoN SIGNS f Install the unit in a place where it is strong enough to hold the product weight . When installed in place where it is not strong enough to support the product weight, the unit may fall and cause injury . f Wrap the product in thermal insulation if it is installed in a ceiling void which has outside air introduced to it .
  • Page 5: Space Requirement

    Space requirement ✴✴026✴✴ 600 mm Exhaust air Outdoor air Body Heat exchange element Inspection hole (for filter, heat exchange element, fan, motor and damper) Return air Supply air • The ERV should be installed in a ceiling which has enough space above as seen in the picture . 20 mm NotE 370 mm...
  • Page 6 Space requirement ✴✴035/050/080/100✴✴ Body Return air Supply air Space for repairing Inspection hole (for filter, heat exchange element, fan, motor and damper) Exhaust air Outdoor air Heat exchange element Unit: mm Model Number of heat exchange elements 1000 ✴✴035/050✴✴ 1135 ✴✴080/100✴✴...
  • Page 7: Installation Diagram

    Installation diagram ✴✴026✴✴ Supply air duct anchor bolt Exhaust air duct Supply air Hood air discharging hole (air exhaust grille) 3 m Return air air intake hole (air exhaust grille) Exhaust air Insulation Return air duct Outdoor air suction duct Hood ✴✴035/050/080/100✴✴...
  • Page 8 Installation diagram • Install the unit in a place where it is strong enough to hold the product weight . • Install the unit in a place where the space is enough for repair and other service . CAUtIoN • Do not install the product in places with high temperature and humidity (such as swimming pool, sauna, bathroom etc .
  • Page 9: External Dimension

    External dimension ✴✴026✴✴ Outdoor air Return air Supply air Exhaust air ❇ ❈ nominal diameter for duct : Ø150 mm Name Quantity ① Maintenance cover ② Heat exchange element ③ Dust filter ④ Hanger ⑤ Electrical component box Unit: mm Model ø 140 ø 156 ✴✴026✴✴...
  • Page 10 External dimension ✴✴035/050/080/100✴✴ Exhaust air Return air Outdoor air Supply air Model Nominal diameter for duct Ø200 ✴✴035/050✴✴ Ø250 ✴✴080/100✴✴ Name Quantity ① Maintenance cover ② Heat exchange element ③ Dust filter ④ Hanger ⑤ Electrical component box Unit: mm Model 1000 1012...
  • Page 11: Hanging The Erv

    Hanging the ERV Ensure correct installation - poor installation may result in malfunction or injury, due to the product falling . 1 . Insert bolt anchors to a ceiling . Use existing ceiling support or construct a suitable support . 2 .
  • Page 12: Electric Wiring

    Electric wiring Before electric wiring, make sure that the voltage is 1 wire 220~240 V, 50 Hz/60 Hz . Electrical component box Surface ✴✴026✴✴ ✴✴035/050/080/100✴✴ Maintenance cover Hanger Use a cable tie here, to retain the cable Electrical component box Maintenance cover Hanger Electrical component box Use a cable tie here, to retain the cable...
  • Page 13 Electric wiring 1 . Remove the 4 screws on the electrical component box and open the cover plate . Screw Screw Maintenance cover Cable fixation Electrical component box Electrical component box [✴✴026✴✴] [✴✴035/050/080/100✴✴] 2 . Connect the cables correctly as seen in the picture . - Fix the cables with a cable tie .
  • Page 14 Electric wiring Main PCB ① ⑤ ⑥ ⑦ ⑧ ⑨ ⑩ ② ⑪ ③ ⑱ ④ ⑫ ⑯ ⑰ ⑬ ⑲ ⑭ ⑳ ⑮ Part name description Part No. ① Download Program downloader connector Cn301(BlK) ② EEPROM SUB PBa Cn201(WHT) ③...
  • Page 15 How to connect your extended power cables 1 . Prepare the following tools . tools Crimping pliers Connection sleeve (mm) Insulation tape Contraction tube (mm) Spec MH-14 20xØ6 . 5 (HxOD) Width 19mm 70xØ8 . 0 (lxOD) Shape 2 . as shown in the figure, peel off the shields from the rubber and wire of the Power cable power cable .
  • Page 16 Electric wiring 5 . Wrap it with the insulation tape twice or more and position your contraction tube in the middle of the insulation tape . a total of three or more layers of insulation is required . f Method 1 f Method 2 Insulation tape Insulation tape...
  • Page 17: Schematic Diagram

    Schematic diagram OPTIOn OPTIOn OPTIOn OPTIOn OPTIOn OPTIOn: Power and Communication cables specification Power Cable Communication Cable 2 . 0  mm 0 . 7 5 mm (VCTF) ❇ ❇ The power and communication cables are not supplied with ERV unit . • Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord .
  • Page 18: Connecting The Unit

    Connecting the unit Make sure to disconnect the power cable and power supply before connecting the ERV to other control solutions . If not, it may cause malfunction due to electrical interference . ERV interface module It does not need to connect the ERV interface module in case of individual control . Connect the ERV interface module to the MaSTER ERV only, in case of centralized control .
  • Page 19 ERV wired remote controller and multiple ERVs ERV Wired Remote Controller F3, F4 1 . Remove the back cover of the ERV wired remote controller . 2 . Connect the COM a (F3), COM B (F4) of the ERV wired remote controller to the F3, F4 terminal of the ERV PCB . 3 .
  • Page 20 Connecting the unit Control setting for the onoff controller Setting centralized individual control (1:1, Individual room control) f For centralized individual control, RMC address of each ERV must be set differently from the OnOff controller . OnOff controller ERV interface module "0" MaIn:4 MaIn:0 MaIn:1...
  • Page 21 Setting centralized group control (1:1 group, simultaneous control of 16 groups) f For centralized group control, RMC address of all ventilation systems must be set equally from the OnOff controller . Maximum 16 units can be set in same RMC address . OnOff controller ERV interface module "0"...
  • Page 22 Connecting the unit Setting simultaneous control of onoff controller and ERV wired remote controller f The OnOff controller can be controlled via RMC address of the ERV, while the ERV wired remote controller can be controlled via F3, F4 . OnOff controller MaIn:0 RMC:2...
  • Page 23 Connecting ERV 1500CMH, 2000CMH This instruction is to connect two 800CMH units to use as 1500CMH or connect two 1000CMH units to use as 2000CMH . • after installing 1500CMH, 2000CMH model, you can set 2 ERV units as a zone in DMS setting but they will operate individually .
  • Page 24 Connecting the unit Setting centralized individual control f For centralized individual control, RMC address of each ERV must be set equally from the OnOff controller . OnOff Controller ERV interface module "0" MaIn:0 MaIn:1 RMC:0 RMC:0 • If you turn on the switch no . 00 of the OnOff controller, ERV with RMC address 0 will be turned on and starts to operate .
  • Page 25 trial operation of the ERV trial operation f Start the trial operation by pressing the KEY1 button below the display (7-segment) . Press the KEY1 button again to end the trial operation . will be displayed on the display 1 during trial operation . description of ERV display SEG1: Displays "U"...
  • Page 26 Connecting the unit Error Code display Classifications Explanation Error Code Indoor temperature sensor (Short/Open) Outdoor temperature sensor (Short/Open) Sensor error (Carbon dioxide) sensor (Short/Open) Outdoor humidity sensor error Sa (Supplied air) fan motor error Fan error Ea (Exhaust air) fan motor error Error due to repeated MaIn address System down due to communication error after tracking has been complete Communication error...
  • Page 27: Installing The Duct

    Installing the duct duct connection f Wind the aluminum tape securely around duct connections to prevent any air leak . f Try to install indoor side supply air duct and exhaust air duct as far as possible from each other . f aspect ratio should be changed to less than 1:4 when cylindrical duct is changed to rectangular duct .
  • Page 28 Installing the duct Examples of bad duct installation Extreme bend Multiple bend narrow connection part Installation standards for damper of ERV (for preventing back draft, cold draft and condensation) (should be purchased separately) Classification outdoor air Exhausted air Supplied air Returned air Type of damper Motorized damper...
  • Page 29: Performance Graph

    Performance graph ✴✴026✴✴ Fan characteristics Efficiency Turbo High Temperature Cooling-Enthalpy Heating-Enthalpy air volume (CMH) air volume (CMH) ✴✴035✴✴ Fan characteristics Efficiency Turbo High Temperature Cooling-Enthalpy Heating-Enthalpy air volume (CMH) air volume (CMH) ✴✴050✴✴ Fan characteristics Efficiency Turbo High Temperature Cooling-Enthalpy Heating-Enthalpy 1000 air volume (CMH)
  • Page 30 Performance graph ✴✴080✴✴ Fan characteristics Efficiency Turbo High Temperature Cooling-Enthalpy Heating-Enthalpy 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1100 1200 1300 air volume (CMH) air volume (CMH) ✴✴100✴✴...
  • Page 31: Final Checks And Trial Operation

    final Checks and trial operation final checklist Check the follows after the installation . f Installation location and its strength f Inspection hole installation f Wiring f Insulation Check the operating condition and damper operation . Setup the ERV wired remote controller Checks function Air volume...
  • Page 32: Setting Address Of The Erv And Installation Option

    Setting address of the ERV and installation option Procedure of option setting f Setting can be done by using a Samsung air conditioner wireless remote controller for indoor units . (Should be purchased separately . ) Entering mode for option setting mode...
  • Page 33 option setting Status 1 . Setting SEG2, SEG3 option Press [Fan ∨] button to enter SEG2 value . Press [Fan ∧] button to enter SEG3 value . SEG2 SEG3 Each time you press the button,   …  will be selected in rotation . 2 .
  • Page 34 Setting address of the ERV and installation option option setting Status 13 . Setting SEG16, SEG17 option Press [Fan ∨] button to enter SEG16 value . Press [Fan ∧] button to enter SEG17 value . Each time you press the button,  …  will be selected in rotation . SEG16 SEG17 14 .
  • Page 35 Setting the address of ERV (MAIN/RMC) 1 . Check whether power is supplied to the ERV or not . - When the power is not supplied to the ERV, there should be additional power supply to it . 2 . Depending on the installation condition of the ERV, each ERV's address (MaIn/RMC) should be set . 3 .
  • Page 36 Setting address of the ERV and installation option Setting the installation option of the ERV (suitable for the condition of each installation location) 1 . Check whether power is supplied to the ERV or not . - When the power is not supplied to the ERV, there should be additional power supply to it . 2 .
  • Page 37 Use of external Description Page Use of CO sensor damper Indication Details Indication Details Indication Details no function no function no function Indication Disable Disable and Details Enable Enable Option SEG19 SEG20 SEG21 SEG22 SEG23 SEG24 Temperature setting of level setting Description Page Use of humidity sensor...
  • Page 38 Setting address of the ERV and installation option Installation/service mode of wired remote controller Additional functions of ERV wired remote controller SEG used Sub menu Main menu left Right Exit Up and down Set, Cancel 1 . If you want to use the various additional functions for your wired remote controller, press the [Mode] and [ ] buttons at the same time for more than three seconds .
  • Page 39 Installation/service setting mode • If communication initialization is needed after the setting, the system will reset automatically and communication will be initialized . NotE Main Page function factory setting Range Remarks menu menu number Main address Setting/checking Main address of main address target [00H~4FH(hexadecimal)]...
  • Page 40 Setting address of the ERV and installation option 1)* The total option codes are 24 digits . You can set six digits at a time and it is distinguished by page number . Press the [Timer] button to go to the next page . • Options can be set from SEG1 to SEG24 - SEG1, SEG7, SEG13, and SEG19 are page option so they cannot be set nor be displayed .
  • Page 41 Changing a particular option ❇ ❇ Particular option can be set with a wireless remote controller only . You can change each digit of set option . Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 Option mode to Tens digit of option Unit digit of option Description Page...
  • Page 42 Memo ENGLISH-42...
  • Page 43 ENGLISH-43...

Table of Contents