13.3 Sensor / Gas Selection

13.3.1 Sensor Selection
"Select Sensor" sets the identity of the type of mV sensor attached to the XCD RFD when
it does not detect the sensor type automatically.
The available mV sensors:
Cb-2
Cb-3
Cb-4
Cb-5*
Cb-6
Cb-7
Ir-5*
Ir-7
Ir-8*
Selecting '' will move the operator to the Select Sensor screen. The first screen displays
the currently configured sensor. To select a new mV sensor like remote type sensors (Ir-7,
Cb-3 and Cb-4), use'' to move through the list, and then use '' to make the selection
or discard the selection and return to menu mode by using abort function. If type of sensor
is changed, calibration prompt will appear to ask if you want to perform calibration.
13.3.2 Gas Selection
Use "SEL gAS" to set the target gas for sensors capable of detecting multiple gases.
The available gases:
Sensor type
Cb-3
Cb-4
Cb-5*
Cb-6
Cb-7
Sensepoint HT 20%LEL remote
Sensepoint HT 100%LEL remote
Sensepoint 100%LEL remote
Flammable CAT 0-100%LEL remote
705 100%LEL remote (CSA Certified)
705 HT 100%LEL remote
Carbon Dioxide IR 0-2%VOL only remote
Methane IR 0-100%LEL remote
Propane IR 0-100%LEL remote
Diagram 15: Sensor Selection
Gas type
Str 1 to Str 8
Str 1 to Str 8
Str 1 to Str 8
Str 1 to Str 8
Str 1 to Str 8
44
SPXCDHMRFEN Issue 4_08-2016
Gas Name displayed
FLM
FLM
FLM
FLM
FLM