Compact booster unit - single pump to ensure the quality of potable water according to en1717
Table of Contents

Advertisement

Quick Links

CBU144
Compact Booster Unit - single pump
To ensure the quality of potable water according to EN1717
Instructions

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell CBU144 Series

  • Page 1 CBU144 Compact Booster Unit - single pump To ensure the quality of potable water according to EN1717 Instructions...
  • Page 2: Table Of Contents

    4. Technical data ...................10 16. Proof of Maintenance ...............25 4.1 Construction dimensions ..............11 4.2 Noise expectancy values ..............11 4.3 Authorised environmental conditions ..........11 5. Shipping ....................12 5.1 Check condition upon delivery ............12 5.2 Transportation ..................12 Honeywell GmbH Translation of original - EN1H-1374GE23 R1014...
  • Page 3: Safety Guidelines

    Unauthorised operation types The limits that are stated in the documentation have to always be complied with. The delivered system is only guaranteed to operate reliably when it is used as intended. EN1H-1374GE23 R1014 - Translation of original Honeywell GmbH...
  • Page 4: Residual Dangers In Handling The Compact Booster Unit

    - Hazard to persons caused by electrical, thermal, mechanical, and chemical influences - Loss of important product functions - Failure to perform required maintenance and service measures - Environmental hazard caused by leakage of hazardous substances Honeywell GmbH Translation of original - EN1H-1374GE23 R1014...
  • Page 5: Basic Safety Measures

    1.11 Requirements for operating personnel compact booster unit. 1.11.1 Operating personnel Parts and special equipment not delivered by Honeywell are also not autho- This compact booster system may only be asembled, started, operated, rised by Honeywell for use. maintained, and shut down by persons who have been trained, instructed and authorised to do so.
  • Page 6: General Information

    Instructions for the pressure switch In order to maintain the warranty, in the event of damage immediately Instructions for the throttle valve contact the nearest Honeywell service centre. Instructions for the membrane pressure vessel Conformity with the following norms Instructions for the check valves...
  • Page 7: Description

    Version The Compact Booster Unit consists of the following modules, that can be Honeywell Compact Booster Unit - single pump CBU144 as a safety device disassembled (for example for transport purposes). to separate potable water from category 5 fluids according to DIN EN 1717 •...
  • Page 8: Function

    • Water shortage Figure 2: CBU144 CBU144Inlet side • Switch to position manual/automatic • Buffer tank overflow • Remote actuation via remote on/off • Collective error message • Separation of potable water Honeywell GmbH Translation of original - EN1H-1374GE23 R1014...
  • Page 9: Mode Of Operation

    (default 90 °C) to protect the pump against overheating when operated without a minimum amount discharge. Temperature monitoring is activated in the automatic and manual modes. EN1H-1374GE23 R1014 - Translation of original Honeywell GmbH...
  • Page 10: Technical Data

    G2 1/2 DN80 26.35 CBU144-80B-094 G2 1/2 DN80 18.5 32.1 CBU144-80B-104 G2 1/2 DN80 10.2 12.1 18.5 32.1 CBU144-80B-114 G2 1/2 DN80 11.2 13.4 18.5 32.1 CBU144-80B-125 G2 1/2 DN80 12.2 14.5 38.1 Honeywell GmbH Translation of original - EN1H-1374GE23 R1014...
  • Page 11: Construction Dimensions

    All dimensions in mm unless stated otherwise. Noise expectancy values Refer to pump manual for noise value of a single pump. Authorised environmental conditions Ambient temperature 5°C ...40°C Relative air humidity max. 80% r.F. EN1H-1374GE23 R1014 - Translation of original Honeywell GmbH...
  • Page 12: Shipping

    2. In the case of transport damage estimate the extent, document the Danger for persons, near-by systems and the the environment that damage and notify Honeywell immediately in writing. arises from the non-intented use of the compact booster unit. Transportation Operate the compact booster unit only as intended.
  • Page 13: Inspection Before Assembly

    Installing valves All additional valves in the terminal lines such as sliders, water meters and check valves have to be dimensioned according to the values stipulated by the competent water distribution company. EN1H-1374GE23 R1014 - Translation of original Honeywell GmbH...
  • Page 14: Electrical Connection

    Forward alert messages to the control unit. The clamps are labelled in the diagram and in the cabinet. Potential-free collective error message can be created by looping throu- gh of potential-free single messages. Honeywell GmbH Translation of original - EN1H-1374GE23 R1014...
  • Page 15: Standby Indicator

    7.11 Standby indicator Initial operation The system standby mode has to be registered by the operator or their The initial start-up should be performed by Honeywell technical staff. contractors at the responsible authority (most commonly WVU or factory Caution inspectorate). Before starting the system, the author has to certify that the prerequisites for connection are fulfilled.
  • Page 16: Settings

    1. Secure the shut-off valves of the in and output against being closed. 2. Operate the main switch to supply the system with voltage. - The green light goes on to signal standby mode. Honeywell GmbH Translation of original - EN1H-1374GE23 R1014...
  • Page 17: Maintenance

    Maintenance should be performed by Honeywell technical staff. Inappropriately maintained compact booster unit • If necessary contact the service department at Honeywell. The proper function of the compact booster unit can no longer be Performance of tasks only by qualified personnel (see section 1.11).
  • Page 18: Monitoring Operation

    Check the batteries yearly, replace if necessary. Observe the manufacturer`s manual on how to use the rechargable backup battery. Honeywell GmbH Translation of original - EN1H-1374GE23 R1014...
  • Page 19: Maintenance

    10. Troubleshooting Maintenance Maintenance should be performed by Honeywell technical staff. During the warranty period consult the manufacturer before performing Alterations or modifications of the system are only permitted with the maintenance work on the system (only work that is required for start-up consent of the manufacturer.
  • Page 20: Possible Causes / Elimination

    The refilling is too large, odour trap is Check the refilling, check if the odour ------------------------ clogged trap is clogged, clean if necessary Honeywell GmbH Translation of original - EN1H-1374GE23 R1014...
  • Page 21: Shut-Down, Restart

    2. Separate the pump materials for example according to: - Metal - Plastic - Electronic junk - Grease and lubricants 3. Dispose according to local regualtions or have them disposed of accor- ding to regulations. EN1H-1374GE23 R1014 - Translation of original Honeywell GmbH...
  • Page 22: Spare Parts

    DN80 0904136 Movitec 4006 DN80 0904137 Pressure switch MCS 22 0904106 Solenoid valve 1/2" 0904107 Floating valve DN50, DN65 VR170-2A DN80 VR170-21/2A Float switch 0904116 Spare parts for older models on request Honeywell GmbH Translation of original - EN1H-1374GE23 R1014...
  • Page 23: Start-Up Protocol

    15. Start-up protocol The following so-called Honeywell Compact Booster Unit was commisioned today by the signatories, authorised Honeywell customer service staff, and this protocol was written. 1 Compact booster unit Series ..................Size ..................Serial number ..................Order number ..................
  • Page 24: Declaration Of No Objection

    The following safety precautions regarding rinsing medium, residual fluids and their disposal are required: .................................................................. We ensure that the above information is correct and complete and delivery will be made according to statutory requirements............................................City, date and signature Address Company stamp Honeywell GmbH Translation of original - EN1H-1374GE23 R1014...
  • Page 25: Proof Of Maintenance

    This compact booster unit is subject to the standards for potable water and guidelines for maintenance therein, and have to be maintained regularly by qualified personnel and the results have to be documented. Date Operating company Name Signature EN1H-1374GE23 R1014 - Translation of original Honeywell GmbH...
  • Page 26 Automation and Control Solutions Manufactured for and on behalf of the Environmental and Combustion Controls Division Honeywell GmbH of Honeywell Technologies Sàrl, Z.A. La Pièce 16, Hardhofweg 1180 Rolle, Switzerland by its Authorised Repre- sentative Honeywell GmbH 74821 MOSBACH EN1H-1374GE23 R1014...