3.2.6.18
REG630
Application Manual
COMMON OPERATE
COMMON OPERATE
CBFP_RETRIP
COMMON OPERATE
COM
X304
AVR Trip
9
BI 07
6
BI 08
Turbine trip
10
GUID-2E7633C0-AA19-46E1-804B-24A6E1EE9825 V1 EN
Figure 17:
Tripping logic

Combined operate and start alarm signal

The operate outputs of all the protection functions (except for underpower protection),
and the external trip from AVR and turbine are combined in the OR-gate to get a
common Operate output. In addition, the activation of binary input COM101.BI12,
that is, the low pressure lockout will also trip the generator circuit breaker. This
common operate signal is connected to a tripping logic. It is also available as an alarm
binary output, PSM SO1, with a settable minimum alarm delay of 80 ms.
Similarly, a common Start output is derived from the start outputs of all the protection
functions (except for underpower protection) combined in an OR-gate. The output is
available as an alarm binary output PSM SO2 with a settable minimum alarm delay of
80 ms.
These combined operate and start signals are also connected to trigger the disturbance
recorder.
MASTER TRIP
TRPPTRC(1)
BLOCK
TRIP
OR
OPERATE
CL_LKOUT
RST_LKOUT
CB_OPEN_CMD
TRPPTRC(2)
OR
BLOCK
TRIP
OPERATE
CL_LKOUT
RST_LKOUT
BREAKER FAILURE PROTECTION
CCBRBRF
3I> / I > BF
0
51BF / 51NBF
3I
TRRET
I0
TRBU
START
CB_FAULT_AL
CB CLOSE
POSCLOSE
CB_FAULT
BLOCK
COMMON OPERATE
COMMON
OR
OPERATE
COMMON START
Section 3
REG630 variants
PSM
PO1
X327
1
Open CB
TCS1
2
PO3
5
Open CB
TCS3
6
CBFP_RETRIP
CBFP BACKUP TRIP
PSM
X327
13
SO1
Common operate
14
PSM
X327
15
SO2
Common start
16
43