Input/Output Signal Interface - ABB RELION 630 Series Applications Manual

Generator protection and control
Hide thumbs Also See for RELION 630 Series:
Table of Contents

Advertisement

1MRS757582 C
3.2.3
REG630
Application Manual

Input/output signal interface

Table 6:
Binary input interface
Hardware module
Hardware channel Usage
instance
COM
BI1
COM
BI2
COM
BI3
COM
BI4
COM
BI5
COM
BI6
COM
BI7
COM
BI8
COM
BI9
COM
BI10
COM
BI11
COM
BI12
COM
BI13
COM
BI14
The IED outputs are categorized as power outputs (POx) and signal outputs (SOx).
The power outputs can be used for starting and stopping the motor. The signal outputs
are not heavy-duty outputs. They are used for alarm or signalling purposes.
Table 7:
Binary output interface
Hardware module
Hardware channel Usage
instance
PSM
PO1
PSM
PO2
PSM
PO3
PSM
PO4
PSM
PO5
PSM
PO6
PSM
SO1
PSM
SO2
PSM
SO3
The IED measures the analog signals needed for protection and measuring functions
via galvanically-isolated matching transformers. The matching transformer input
channels 1...7 are intended for current measuring, and the channels 8...10 for voltage
measuring.
Generator circuit breaker close
Generator circuit breaker open
Generator circuit breaker truck close
Generator circuit breaker truck open
Earthing switch close
Earthing switch open
NGR switch close
NGR switch open
Operate signal from AVR
Operate signal from turbine
Lockout reset
Generator circuit breaker gas pressure (lockout)
Generator circuit breaker spring charged
Voltage transformer MCB open
Master Trip 1 (generator circuit breaker open)
Generator circuit breaker close enable signal
Master Trip 2 (generator circuit breaker open)
Operate from directional over power protection
Operate from differential protection
Operate from frequency protection
Common generator circuit breaker operate signal
Common generator circuit breaker start signal
Generator circuit breaker trip circuit and monitoring alarm
Section 3
REG630 variants
27