REG630 variants

Presentation of preconfigurations

The 630 series protection relays are offered with optional factory-made
preconfigurations for various applications. The preconfigurations contribute to faster
commissioning and less engineering of the protection relay. The preconfigurations
include default functionality typically needed for a specific application. Each
preconfiguration is adaptable using the Protection and Control IED Manager
PCM600. By adapting the preconfiguration the protection relay can be configured to
suit the particular application.
The adaptation of the preconfiguration may include adding or removing of protection,
control and other functions according to the specific application, changing of the
default parameter settings, configuration of the default alarms and event recorder
settings including the texts shown in the HMI, configuration of the LEDs and function
buttons, and adaptation of the default single-line diagram.
In addition, the adaptation of the preconfiguration always includes communication
engineering to configure the communication according to the functionality of the
protection relay. The communication engineering is done using the communication
configuration function of PCM600.
If none of the offered preconfigurations fulfill the needs of the intended area of
application, 630 series protection relays can also be ordered without any
preconfiguration. In this case the protection relay needs to be configured from the
ground up.
The functional diagrams are divided into sections which each constitute one
functional entity. The external connections are also divided into sections. Only the
relevant connections for a particular functional entity are presented in each section.
Protection function blocks are part of the functional diagram. They are identified
based on their IEC 61850 name but the IEC based symbol and the ANSI function
number are also included. Some function blocks, such as PHHPTOC, are used several
times in the configuration. To separate the blocks from each other, the IEC 61850
name, IEC symbol and ANSI function number are appended with a running number,
an instance number, from one onwards.