Addressable Parameters; Parameter Field Addresses - ABB PointMaster 200 Series Operating Manual

6-channel multipoint recorder, interface description
Table of Contents

Advertisement

Parameters

Addressable parameters

The following parameters can be read or modified with telegrams
SD2 and SD3 (see corresponding sections on pages 7 and 8).
To be able to do this, a parameter field address (see table on
the right), the parameter address (offset, page 10) and the code
of the parameter value are required.
For example
The following information is required for the first chart speed:
Parameter field address
Parameter address (offset)
Code for the chart speed 20 mm/h
Parameter field address
Instrument function group
System parameterisation
Parameterisation, channel 1
Parameterisation, channal 2
Parameterisation, channel 3
Parameterisation, channel 4
Parameterisation, channel 5
Parameterisation, channel 6
Text lines
10H
Print intervals
0000H
Print synchronisation times
04H
Print colours
DI assignment
Date and time
Calibration data
Measured values and equipment status
Sending measured values to the recorder
Reading accounting data (block transfer)
Writing the equipment status
Sending the print line
Sending the display line to the recorder
Communication error register
The above-named addresses are input into the appropriate fields
of a message during communication. From the address, the re-
corder determines the data range to be transmitted. The data
transmission takes place with messages in the SD2 and SD3
formats. To read a data field, FC = 15H must always be used,
FC = 16H must be used to write a data field. If invalid parameter
values are contained in a message, the negative acknowledge-
ment (SD1, FC = 11H) is transmitted by the recorder in reply.
Parameter field
address
10H
11H
12H
13H
14H
15H
16H
17H
18H
19H
1AH
1BH
1CH
1DH
1EH
1FH
20H
21H
F1H
F2H
FFH
Parameters 9