Product ID (Input registers at addresses 0000 to 007F)
PRODUCT
0000
ID
0001
0002
0003
0004
↓
007F
Actual Values (Input registers at addresses 0200 to 0FFF)
MOTOR
0200
STATUS
0201
0202
↓
020F
TRIP
0210
DATA
0211
0212
↓
021F
LINE
0220
CURRENT
0221
0222
0223
0224
LINE
0225
VOLTAGE
0226
0227
0228
0229
*
Range for collector-ring motors.
** Range for brushless motors.
1. The access password must be written correctly before any setpoints can be written via Modbus. The password is initially the same as the default password,
9
but the two passwords are stored separately, so the keyboard can not be used to change the communications password and vice-versa.
2. The allowable range of FLA is as follows: the minimum full load amps value is 2/5 times the CT ratio; the maximum is equal to the CT ratio.
3. The locked rotor current is range dependent on the FLA setpoint: the minimum is twice the full load amps and the maximum value is 12 times the FLA.
4. REGULATOR OUTPUT must be greater than or equal to FLOOR VOLTS, likewise FLOOR VOLTS must be less than or equal to REGULATOR OUTPUT.