Page 1
They have a liquid-filled, remote thermal element. APPLICATION Typical applications for the LP916A are duct-mounted (Fig. 1) and mixed air control (Fig. 2). The LP916B is typically used for fan coil unit control (Fig. 3). Typical applications for the reverse acting LP916C are cooling coil control similar to Figure 1 or fan coil control (Fig.
Do not bend the capillary When temperature at the sensing element falls below setpoint tubing in a short radius. of the LP916A, branchline pressure to the normally open (n.o.) valve is lowered, and the valve is modulated open to maintain setpoint temperature.
Replace the knob and position the pointer to correspond to the temperature sensed by the remote bulb. LP916B For direct action, follow Steps 1 through 5 for LP916A and C. For reverse action (except LP916B1058), apply 13 psi (90 kPa) main-line pressure. For the LP916B1058, apply 9 psi (62 kPa) main-line pressure.
LP916A-C PNEUMATIC REMOTE BULB THERMOSTATS TROUBLESHOOTING Before troubleshooting the LP916, check branchline piping and actuators for leaks. Refer to Figure 7 to troubleshoot the LP916 Thermostat. BEGIN MAKE OPERATIONAL CHECK CHECK MAIN OPERATES CHECK PROPERLY CALIBRATION PRESSURE CORRECT DISCONNECT PRESSURE...
Page 7
LP916A-C PNEUMATIC REMOTE BULB THERMOSTATS REPAIR The only repair recommended for the LP916 is the GASKET replacement of the plate and tube assembly, gaskets, restriction plate, and filters with connector assembly and CONNECTOR gasket. Since February 1984, models have a different...
LP916A-C PNEUMATIC REMOTE BULB THERMOSTATS PARTS AND ACCESSORIES PARTS LIST See Figure 9 for LP916A &C exploded view and Figure 10 for LP916B exploded view. See Tables 2 and 3 for LP916A &C parts list and Tables 3 and 4 for LP916B parts list.
Page 9
LP916A-C PNEUMATIC REMOTE BULB THERMOSTATS S22649 Fig. 9. LP916A and C Exploded view (See Tables 2 and 3). 75-5559...
Page 10
LP916A-C PNEUMATIC REMOTE BULB THERMOSTATS Table 3. LP916A-C Element and lever assemblies. Assembly Part No. Part No. Bulb Size in. (mm) 316372A A1001, A1027, A1068, B1009, 3/8 x 9-1/2 B1025, B1041, B1066, C1007, (9.5 x 241) C1023 316372B A1019, B1017, B1058, C1049...
Page 12
By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’...