Selective Fire Alarm Presentation; Alert Annunciation Units 1735 & 1736 - Panasonic 1735 Technical Description

Alert annunciation units
Hide thumbs Also See for 1735:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01295 Rev: 2
4
4.1
Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x

Selective Fire alarm presentation

Normally all fire alarms will be presented in the c.i.e:s, ext. FBP:s and
Presentation units, etc. There are some possibilities to select which
alarms that shall be presented in each unit. It is also programmable, if
the fire alarm presentation shall be according to EN54, i.e. when only
one point in a zone is in alarm status it will be presented as a point
alarm (zone and address), else presented as a zone alarm.
Alert Annunciation Units 1735 & 1736
The alarm presentation in an AA unit will be like in the c.i.e. that the
AA unit is connected to, i.e. point alarm or zone alarm presentation.
See Operating Instructions, chapter "Fire alarm" for the system
respectively.
Via Win512 / Win128 / Win512 G3, it is possible to select which
alarms that shall be presented in the AA unit respectively.
example, if there are many buildings in an installation, the AA unit in
one specific building shall only present alarms activated within this
building.
The following, so called operands are available (CU alternatives not
valid for EBL128):
1. Control unit (CU)
2. Consecutive control units (CU1, CU2)
3. Zone (zone)
4. Consecutive zones (zone1, zone2)
5. Zone – address (zone, addr)
6. Consecutive zone – addresses (zone1, addr1, zone2, addr2)
Explanations:
1. CU = Control unit number (c.i.e. no. 00-29)
2. CU1 = The first control unit number in the sequence. CU2 = The
last control unit number in the sequence.
3. zone = Zone number (001-999) In EBL128 (01-32).
4. zone1 = The first zone number in the sequence. zone2 = The last
zone number in the sequence.
5. zone, addr = Zone number and address within the zone (001, 01 –
999, 99)
6. zone1, addr1 = The first zone number and address in the sequence.
zone2, addr2 = The last zone number and address in the sequence.
Up to 50 operands can be used to make a, so called selector for an AA
unit. Here follows a selector example:
Control unit (00), Consecutive zones (100, 500), Zone – address
(900, 01) In this AA unit will only be presented alarms that origin
from the c.i.e. no. 00 or from zone 100 up to and including zone 500
or from the alarm point 900-01.