Panasonic 1735 Technical Description

Panasonic 1735 Technical Description

Alert annunciation units
Hide thumbs Also See for 1735:

Advertisement

Quick Links

Technical Description
MEW01295
Revision 2
Alert Annunciation Units 1735 & 1736,
ver. 1.4.x
Author:
Jan Pettersson
Date of issue: 2010-04-07
Date of rev:
2011-08-15

Advertisement

Table of Contents
loading

Summary of Contents for Panasonic 1735

  • Page 1 Technical Description MEW01295 Revision 2 Alert Annunciation Units 1735 & 1736, ver. 1.4.x Author: Jan Pettersson Date of issue: 2010-04-07 Date of rev: 2011-08-15...
  • Page 2 This page has deliberately been left blank.
  • Page 3: Table Of Contents

    Panasonic Electric Works Nordic AB MEW01295 Rev: 2 Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x Table of contents Introduction________________________________ 3 Definitions / Explanations ____________________ 4 General description _________________________ 5 Alert Annunciation Unit 1735 _________________________ 5 3.1.1 SW mode 1735 - 1587 ___________________________ 6 Alert Annunciation Unit 1736 _________________________ 6 3.2.1...
  • Page 4: Alert Annunciation Units

    Panasonic Electric Works Nordic AB MEW01295 Rev: 2 Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x Revision history ____________________________ 35 This page has deliberately been left blank.
  • Page 5: Introduction

    The Alert annunciation units 1735 & 1736 can be used in the systems EBL512, EBL128 and EBL512 G3. In system EBL512 G3 the 1735 / 1736 a software version > 1.4.x. has to be used. Original file name: L:\User documents\EBL\Doc\Eng\MEW01295 (Rev...
  • Page 6: Definitions / Explanations

    Panasonic Electric Works Nordic AB MEW01295 Rev: 2 Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x Definitions / Explanations Definitions / explanations / abbreviations / etc. frequently used or not explained elsewhere in the document. Alert Annunciation Alert Annunciation Unit...
  • Page 7: General Description

    Panasonic Electric Works Nordic AB MEW01295 Rev: 2 Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x General description When the Alert Annunciation function shall be used in the systems EBL512, EBL128 and EBL512 G3, one or more AA units are required to present the AA alarms and for the related manoeuvres, i.e.
  • Page 8: Sw Mode 1735 - 1587

    3.1.1 SW mode 1735 - 1587 The Alert Annunciation Unit 1735 has to run in SW mode 1735 – 1587. 1735 succeeds the existing Display unit with alert annunciation 2235SE (with Swedish designation texts) but not as a spare part, since the 2235SE unit is connected to a COM loop.
  • Page 9 "J1" but an optional RS485 transceiver component 4552 is required on the main board. In system EBL512 G3, 1736 units running in SW mode 1735 – 1587 are connected directly to the main board connector "J4".
  • Page 10: Selective Fire Alarm Presentation

    Panasonic Electric Works Nordic AB MEW01295 Rev: 2 Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x Selective Fire alarm presentation Normally all fire alarms will be presented in the c.i.e:s, ext. FBP:s and Presentation units, etc. There are some possibilities to select which alarms that shall be presented in each unit.
  • Page 11 Panasonic Electric Works Nordic AB MEW01295 Rev: 2 Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x Default for each AA unit is, in system EBL512 and EBL512 G3: Control units (00, 29), i.e. all alarms from all c.i.e:s will be presented in all AA units.
  • Page 12: Led Indicators, Push Buttons, Etc

    Panasonic Electric Works Nordic AB MEW01295 Rev: 2 Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x LED indicators, Push buttons, etc. The functions of the LEDs, push buttons, display and buzzer are described below. Alert Annunciation Unit 1735 front Figure 3.
  • Page 13 Panasonic Electric Works Nordic AB MEW01295 Rev: 2 Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x Table of LED indicators: LED indicator Colour Indicating Blinking+ Alarm (Larm) 2 x Red AA alarm (Acknowledge time starts.) "L6" turned on + Buzzer (interm.)
  • Page 14 Panasonic Electric Works Nordic AB MEW01295 Rev: 2 Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x Table of push buttons: Push button Colour Operation / function Alarms queued Used, when LED "L2" (Alarms queued) is turned on, Black (Flera larm) to scroll through the queued alarms.
  • Page 15: Alert Annunciation Unit 1736

    Panasonic Electric Works Nordic AB MEW01295 Rev: 2 Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x Alert Annunciation Unit 1736 The Alert Annunciation unit is also available with a neutral front. The designation texts for the LEDs and push buttons have to be made separately and put into a "text slot"...
  • Page 16 Panasonic Electric Works Nordic AB MEW01295 Rev: 2 Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x Table of LED indicators: LED indicator Colour Indicating (Depending on Blinking+ 2 x Red AA alarm (Acknowledge time starts.) language, etc. "L6"...
  • Page 17 Panasonic Electric Works Nordic AB MEW01295 Rev: 2 Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x Table of push buttons: Push button Colour Operation / function (Depending on Black Used, when LED "L2" is turned on, to scroll language, etc.
  • Page 18: Sw Mode & Address Setting

    Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x SW mode & Address setting Alert Annunciation Unit 1735 can run in SW mode 1735 - 1587 only. It shall also have a unique address on the RS485 line connected to the 1587 board in the EBL512 c.i.e.
  • Page 19: Sw Mode Setting Via Jumper "J4

    Panasonic Electric Works Nordic AB MEW01295 Rev: 2 Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x the unit will automatically be ready for the "Address setting ", see below. 6.1.1 SW mode setting via jumper "J4" An AA unit in operation will be ready for the "SW mode setting"...
  • Page 20: Flow Chart

    H5/A9 (A7 in system EBL512 G3), see Operating instructions for the system respectively. Flow chart On the following page is a flow chart, showing the SW mode setting, Language setting , Address setting, etc. Language setting is not valid for the AA units 1735 & 1736.
  • Page 21 Panasonic Electric Works Nordic AB MEW01295 Rev: 2 Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x Power on / Restart / Reset via "JP1" "J4" ON? SW mode selected? SW mode setting Normal operation Address SW mode command from xxxx - 1587? c.i.e.
  • Page 22: User Definable Text Messages (Alarm Texts)

    Panasonic Electric Works Nordic AB MEW01295 Rev: 2 Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x User definable text messages (alarm texts) In the c.i.e., each alarm point (zone – address) and each zone can have an individual user definable text message (alarm text)
  • Page 23: Commissioning Of A New Unit / Ssd Download

    Panasonic Electric Works Nordic AB MEW01295 Rev: 2 Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x Commissioning of a new unit / SSD download The cable (RS485 line) to the AA unit(s) shall be connected. See connection diagram for the system respectively.
  • Page 24 Panasonic Electric Works Nordic AB MEW01295 Rev: 2 Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x place. During the download to an AA unit, the following will be shown in its display: "SSD download in progress.." 8. After download of SSD to an AA unit, the following will be shown in its display (very quickly): "SSD Download Memory OK"...
  • Page 25: Restart

    Panasonic Electric Works Nordic AB MEW01295 Rev: 2 Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x Restart The AA unit will restart:  When the unit is powered up  If the jumper "JP1" is activated momentarily  After address setting (i.e. "P2" is pressed).
  • Page 26 Panasonic Electric Works Nordic AB MEW01295 Rev: 2 Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x "SSD memory fault" The AA unit will work since the alarm texts will be sent out from the c.i.e. There will also be a fault message in the c.i.e.: In system EBL512: "FAULT:...
  • Page 27: Fault Messages

    Panasonic Electric Works Nordic AB MEW01295 Rev: 2 Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x Fault messages Here follows a list of the fault messages that might be displayed in the AA unit and in the c.i.e. respectively.
  • Page 28: System Ebl128

    Panasonic Electric Works Nordic AB MEW01295 Rev: 2 Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x 10.2.2 System EBL128 "FAULT: No reply AAU x. The contact with the AA unit is interrupted. Check the cable and all connections. Is a correct / complete SSD download (via Win128) performed? Check the address setting, SW mode setting, etc.
  • Page 29: Software (Sw)

    Panasonic Electric Works Nordic AB MEW01295 Rev: 2 Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x Software (SW) The software is stored in a flash memory in each AA unit. This software can be replaced / updated (i.e. downloaded via Win512 / Win128 / Win512 G3).
  • Page 30: Sw Download

    Panasonic Electric Works Nordic AB MEW01295 Rev: 2 Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x 5 The AA unit will restart (Restarting..), i.e. the buzzer will sound for approx. two seconds and the unit will return to normal operation.
  • Page 31: Operation

    Panasonic Electric Works Nordic AB MEW01295 Rev: 2 Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x Operation The LED "Operation" (L6) is indicating if the "Alert Annunciation" function is enabled or disabled When the "Alert Annunciation" function is enabled, the LED "L3"...
  • Page 32 Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x Figure 5. Operation summary for the AA unit 1735. The AA unit 1736 is like 1735 but it also has an LED "Extinguishing" and push buttons "Silence alarm devices" and "Test".
  • Page 33: Connections

    "J1". The jumper "JP8" only has to be on place (shunted) if the unit is the last unit on the line. NOTE! The AA units 1735 & 1736 can in EBL512 only be connected to a 1587 board (not 1582).
  • Page 34 Panasonic Electric Works Nordic AB MEW01295 Rev: 2 Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x Comments to the components: 1.5 A fuse (not replaceable; the whole p.c.b. should be replaced). Terminal block for the unit's connections. "D" connector (9 ways, male), RS232 interface for SW download.
  • Page 35: Technical Data

    Technical data 14.1 Power supply Nominal voltage for the AA units 1735 & 1736 is 24 V DC. The number of AA units that can be power supplied from the c.i.e. is depending on all other units connected to the same RS485 line (i.e. the current consumption).
  • Page 36 Panasonic Electric Works Nordic AB MEW01295 Rev: 2 Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x Unit Current consumption Quiescent (mA) Active (mA) 12 V DC 24 V DC 12 V DC 24 V DC AA unit 1735...
  • Page 37 Panasonic Electric Works Nordic AB MEW01295 Rev: 2 Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x Revision history Revisions are, when possible, written with red font colour. Revision 1 ‎ Info. revised. ‎ 3 .2 Figure 2 corrected.
  • Page 38 Panasonic Electric Works Nordic AB MEW01295 Rev: 2 Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x...
  • Page 39 This page has deliberately been left blank.
  • Page 40 Panasonic Electric Works Nordic AB Jungmansgatan 12, SE-211 19 Malmö, Sweden Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99 info-fste@eu.pewg.panasonic.com • www.panasonic-fire-security.com...