68 Guidelines for planning the electrical installation
A diagram of the cable routing is shown below.
Control cables
min 200 mm (8 in.)
Input power cable

Separate control cable ducts

Lead 24 V and 230 V (120 V) control cables in separate ducts unless the 24 V cable is
insulated for 230 V (120 V) or insulated with an insulation sleeving for 230 V (120 V).
230 V
(120 V)
24 V
Continuous motor cable shield or enclosure for equipment in the
motor cable
To minimize the emission level when safety switches, contactors, connection boxes or
similar equipment are installed on the motor cable between the drive and the motor:
European Union: Install the equipment in a metal enclosure with 360 degree
grounding for the shields of both the incoming and outgoing cable, or connect the
shields of the cables otherwise together.
90 °
Drive
Motor cable, brake cable
Control cables
230 V
(120 V)
24 V
Motor cable
min 300 mm (12 in.)
Power cable
min 500 mm (20 in.)