Technical Data; Ratings; Safur Resistors - ABB ACS880-07XT Series Hardware Manual

Table of Contents

Advertisement

Technical data

Ratings

Drive module
Basic module
unit type
type
ACS880-
ACS8880-04-
07XT-
U
= 400 V
N
1010A-3
585A-3+P943
1190A-3
650A-3+P943
1330A-3
725A-3+P943
1610A-3
880A-3+P943
U
= 500 V
N
1010A-5
583A-5+P943
1160A-5
635A-5+P943
1310A-5
715A-5+P943
1610A-5
880A-5+P943
U
= 690 V
N
0810A-7
430A-7+P943
0960A-7
522A-7+P943
1080A-7
590A-7+P943
1320A-7
721A-7+P943
P
Maximum continuous braking power. The braking is considered continuous if the braking time
brcont
exceeds 30 seconds.
R
The minimum allowed resistance value of the brake resistor
min
R
Resistance value for the listed resistor assembly
E
Short energy pulse that the resistor assembly withstands every 400 seconds
R
P
Continuous power (heat) dissipation of the resistor when placed correctly
Rcont
The ratings apply at an ambient temperature of 40 °C (104 °F). For 690 V data, please contact your local ABB
representative.

SAFUR resistors

The degree of protection of SAFUR resistors is IP00. The resistors are not UL listed. The
thermal time constant of the resistors is 555 seconds.
Internal brake
chopper per
basic brake
module
P
R
brcont
min
kW
ohm
315
1.3
2xSAFUR200F500
315
1.3
2xSAFUR200F500
400
0.7
3xSAFUR200F500
400
0.7
3xSAFUR200F500
315
1.3
2xSAFUR200F500
315
1.3
2xSAFUR200F500
400
0.7
3xSAFUR200F500
400
0.7
3xSAFUR200F500
285
2.2
SAFUR200F500
350
2.0
2xSAFUR125F500
400
1.8
2xSAFUR125F500
400
1.8
2xSAFUR125F500
Example brake resistor(s) per basic module
Type
ohm
1.35
1.35
0.90
0.90
1.35
1.35
0.90
0.90
2.70
2.0
2.0
2.0
3AXD10000363510, 3AXD00000588487
Resistor braking 165
R
E
P
R
Rcont
kJ
kW
10800
27
10800
27
16200
40
16200
40
10800
27
10800
27
16200
40
16200
40
3600
13
7200
18
7200
18
7200
18

Advertisement

Table of Contents
loading

Table of Contents