Installing The Indoor Units - Samsung DVM S Series Installation Manual

Table of Contents

Advertisement

Installing the indoor units

Model
Example installing
(Each port
connection)
Example installing
(MCU series
connection)
Under 16.0 kW indoor unit : Don't use Y-connector
16.0 kW ~ 28.0 kW indoor unit : Use Y-connector at the Gas & Liquid line
If you want to continuous cooling operation under -5 °C, set outdoor 'Expand
operational temperature range for cooling operation (HR only)' , and use Y-connector on
5.0 ~ 16 kW indoor unit
In case of using Y-connector, it is only connectable for port combination at below
Connectable port combination for Y-connector : A + B port, C + D port, E + F port
Non-connectable port combination for Y-connector : B + C port, D + E port, non-continuous port
Installing indoor
units
Set Dip Switch option for using Y-connector
S/W Option
ON
1
Default
In case of MCU connection in series, the maximum capacity of indoor units in MCU
series connection is 61.6 kW
MCU-S6NEK2N
MCU-S4NEK3N
MCU series connection
MCU
S/W Option
ON
2 3 4
1
2 3 4
Combination of A+B port
MCU-S2NEK2N
MCU
S/W Option
S/W Option
ON
ON
1
2 3 4
1
2 3 4
Combination of C+D port
Combination of E+F port
MCU-S1NEK1N
This unit is only
connectable for one
port under 16 kW
This unit is impossible
to connect MCU to
MCU in series.
61