Size Of The Pipe Connected To The Outdoor Unit - Samsung DVM S Series Installation Manual

Table of Contents

Advertisement

H/P
33.6 kW
40.0 kW
61.6 kW
(1)
(2)
(C)
(A)
(B)
Size of the pipe connected to the outdoor unit (A)
Select the size of the main pipe according to the below table.
Outdoor unit capacity (kW)
(Cooling)
22.4 kW
22.5 kW ~ 28.1 kW
28.2 kW ~ 33.6 kW
33.7 kW ~ 40.0 kW
40.1 kW ~ 45.0 kW
45.1 kW ~ 50.4 kW
50.5 kW ~ 56.0 kW
56.1 kW ~ 63.3 kW
63.4 kW ~ 70.3 kW
70.4 kW ~ 98.4 kW
98.5 kW ~ 135.2 kW
135.3 kW ~ 169.0 kW
169.1 kW ~ 252.0 kW
*Maximum pipe length : The pipe length between an outdoor unit and the farthest indoor unit.
Note1) If Ø 25.40 pipe is not available on site, use Ø 28.58 pipe.
Note2) If Ø 31.75 pipe is not available on site, use Ø 34.92 pipe.
Note3) If Ø 38.10 pipe is not available on site, use Ø 41.28 pipe
❇ For the case that the diameter of the default pipe of an outdoor unit does not match that of the pipe installed on the site,
a socket is provided by default together with the outdoor unit.
Ex.) 135.2 kW
Capacity (kW)
(D)
33.6 kW
73.6 kW
(3)
135.2 kW
(E)
*Maximum pipe length within 90m
Liquid pipe (mm)
Ø 9.52
Ø 12.70
Ø 15.88
Ø 19.05
Ø 22.22
No.
(1)
(2)
(3)
*Maximum pipe length over 90m
gas pipe (mm)
Liquid pipe (mm)
Ø 19.05
Ø 12.70
Ø 22.22
Ø 15.88
Ø 28.58
Ø 19.05
Ø 34.92
Ø 22.22
Ø 41.28
Ø 53.98
Ø 25.40
Pipe size (mm)
Liquid pipe
Gas pipe
Ø 12.70
Ø 28.58
Ø 19.05
Ø 34.92
Ø 19.05
Ø 41.28
gas pipe (mm)
Ø 22.22
Ø 25.40
note1)
Ø 28.58
Ø 31.75
note2)
note3)
Ø 38.10
Ø 41.28
Ø 53.98
note1)
33

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dvm s am080fxvaghDvm s am fxvagr seriesDvm s am100fxvaghDvm s am120fxvaghDvm s am160fxvaghDvm s am140fxvagh ... Show all