RM7838B, RM7838C 7800 SERIES RELAY MODULES
11. Press down arrow to select.
12. "Getting Data" will be momentarily displayed, fol-
lowed by the screen shown in Fig. 14.
Install Postpurge
Edit:
-
Fig. 14. Setting Postpurge time.
This screen allows for setting up the Postpurge for the
RM7838B,C. This will be the time that the Combustion Fan
(terminal 5) will remain energized after the STOP button is
pushed.
13. Use the up arrow to increase the postpurge time.
Time increases:
0 to 60 seconds in 1 second intervals.
60 to 600 seconds in 10 second intervals.
10 to 60 minutes in 1 minute intervals.
14. Press Enter (Left/Right arrow keys simultaneously)
when the correct postpurge time is displayed.
Edit:
-
Fig. 15. Save Changes screen.
15. Use the down arrow to save changes. "Getting Data"
is displayed momentarily.
The following steps are to confirm your selections.
Edit:
-
Fig. 16. Confirmation Acknowledgement screen. (The
Valve Proving Test location is shown.)
32-00211—01
+
M22668
+
M22665B
+
M22670B
16. Press ENTER.
Edit:
-
Fig. 17. Confirmation Correct screen.
17. Use the down arrow to confirm correct. "Getting
Data" will be displayed.
NOTE: Using the up arrow during this step will take you
back to the beginning of the setup routine.
Edit:
Fig. 18. Confirm screen.
18. Press Enter.
Edit:
-
Fig. 19. Confirm Correct screen.
19. Use the down arrow to confirm correct. "Getting
Data" will be displayed.
The following steps are used to confirm your selection.
Edit:
Fig. 20. Confirm Postpurge time.
20. Press Enter.
14
+
-
+
+
-
+
M22671B
M22672A
M22671B
M22674A