997-274-000-6, Issue 6
September 2009
ID3000 Series Installation & Commissioning Manual
A4 - 8
Check that the appropriate jumper link is fitted;
this is dependent upon the connection medium
used for the link, i.e. copper-conductor cable
or optical fibre. Refer to the NGM PCB
instruction sheet (ref: 997-449-000-X) for correct
jumper link setting.
ID
net: Channel 2 Link Fault
2
See 'Channel 1 Link Fault' above.
ID
2
net: Flash Checksum Error
This message indicates a NGM PCB failure.
Action: Replace the NGM PCB.
Note: Other fault conditions may occur in
exceptional circumstances. If this
happens, contact your supplier for
guidance.
ID
2
net duplicate node n
Two nodes have the same node id.
Action: Change the id number of one of the
duplicate nodes (use diagnostic tool).
Power Fault, ID
2
net Booster n
This message indicates an open circuit on the
power fault input of the NGM.
Action: Check for missing or broken wiring.
Check that PSU is not faulty.
4.2 Reconfiguration Warning
Messages
If a panel has already been configured as part
of a Master/Slave network and an attempt is
made to configure it as an ID
network, a warning message is displayed as
follows:
WARNING: this panel is already configured
as a member of a Master/Slave network.
This is incompatible with ID
Peer Network.
If a panel has already been configured as part
of an ID
2
net peer-to-peer network and an
attempt is made to configure it as a Master/
Slave network, a warning message is
displayed as follows:
WARNING: this panel is already configured
as a member of a ID
Network. This is incompatible with Master/
Slave network.
net peer-to-peer
2
net Peer-to-
2
net Peer-to-Peer
2