Heat Pump Equipment; Wiring Conventional Heating And Cooling Equipment To Tz-4 Panel - Honeywell TotalZone TZ-4 Product Data

Zone control panel
Table of Contents

Advertisement

Single Transformer Heating/Cooling
systems require a jumper to be installed
connecting R
and R
H
C
(factory installed).
HVAC Equipment
Heating Transformer
24 VAC
Equip.
Cooling Transformer
First Stage Heating
Second Stage Heating Relay
Third Stage Heating
First Stage Cooling Relay
Second Stage Cooling Relay
Fan Relay
OT
Sensor
DATS
1 "C" terminal connection
is not required on battery
powered, power stealing,
or some electromechanical
thermostats.
2 Leave jumper disconnected
for conventional thermostats.
This diagram shows the typical
three-stage equipment, thermostat,
and damper motor connections.
For specific wiring for other
thermostats, damper motors, and
HVAC Equipment, refer to the
Installation Instructions.
Fig. 16. Wiring conventional heating and cooling equipment to TZ-4 panel.

Heat Pump Equipment

See Fig. 17-22 for heat pump wiring. Refer to manufacturer
instructions for additional wiring details and substitute the
TZ-4 equipment terminals for the thermostat terminals shown.
— Connect the changeover relay to O/B equipment terminal.
— Set switch number 5-7 to on for O (cool) changeover, or to
off for B (heat) changeover.
— Set switch number 5-1 to off for heat pump equipment.
— Set DIP switches 4-1, 4-2, 4-3, and 4-4. See Single Stage
and Multi-Stage Operation in the Operation section.
IMPORTANT
Some heat pump manufacturers (such as York and
Trane) use the B terminal as the transformer
common. Do not connect the common from the
equipment to the zone control panel.
HEAT
LED STATES:
Heat LED
Heating Mode
Flashing Heat LED High Limit
Cool LED
Cooling Mode
R
Flashing Cool LED Low Limit
H
Purge LED
Purge Mode
R
C
Flashing Purge LED Sensor Failure
W
/E
Fan LED
Fan Mode
1
EM Heat LED
EM Heat Mode
W
2
W
/AUX
3
DIP SWITCH S4 SETTINGS
Y
1
1 2ND STAGE OPERATION: TABLE 1
Y
2 2ND STAGE OPERATION: TABLE 1
2
3 3RD STAGE OPERATION: TABLE 1
G
4 3RD STAGE OPERATION: TABLE 1
O/B
5 STAGE TIMER: TABLE 2
6 STAGE TIMER: TABLE 2
7 STAGE TIMER: TABLE 2
OT
8 UNUSED
OT
DIP SWITCH S5 SETTINGS
1 SYSTEM TYPE
DATS
2 DATS LOW LIMIT
DATS
3 PURGE TIME
4 PURGE FAN
5 PURGE DAMPER
6 HEAT FAN
7 O/B ENERGIZED
8 DUAL FUEL
ZONE 1
ZONE 2
2
Thermostat
Damper
Thermostat
W1/
W3/
W1/
C
R
E
Y1
G
O/B Y2
W2
AUX
M6 M4 M1
C
R
E
Y1
L
1
1
C
R
W1
Y1
G
O/B
Y2
W2
W3/
L
C
R
W1
Y1
AUX
Zone 1 Thermostat
Zone 2 Thermostat
4 5 6 Z
1 2 3 X
Power-open
Power-closed
(Opposed Blade
Damper Motors)
COOL
PURGE
FAN
EM. HEAT
ZONE 1
30 F
130 F
140 F
25 F
120 F
150 F
20 F
110 F
160 F
15 F
MAX. DUCT TEMP.
DUAL FUEL OT SETTING
DIP SWITCH S4
O
N
1
2 3 4 5 6 7 8
TABLE 1
#1/#3 #2/#4 OPERATION
1
1
STAT
ON
OFF
1
0
TIMER
1
0
0
1
% ZONES
CONV
HP
0
0
OFF
40F
48F
2.0 MIN
3.5 MIN
HVAC
PANEL
NO CHG
OPEN
HVAC
PANEL
COOL
HEAT
DISABLED ENABLED
ZONE 3
2
Damper
Thermostat
W3/
W1/
G
O/B Y2
W2
AUX
M6 M4 M1
C
R
E
Y1
G
O/B Y2
L
1
G
O/B
Y2
W2
W3/
L
C
R
W1
Y1
G
O/B
Y2
AUX
Zone 3 Thermostat
Power-closed
Power-closed
Spring-open
Spring-open
(Model ZD)
(Model ARD)
ZONE DAMPER MOTORS
M1 - common
M4 - power open
M6 - power closed
Single-Speed Compressor: Wire the compressor to the Y1
terminal.
If the same heat source is used for auxiliary heat and
emergency heat:
— Wire a jumper from W2 (auxiliary heat) to W1/E
(emergency heat).
— Do not connect W3/AUX. See Fig. 17.
If auxiliary heat is separate from emergency heat:
— Connect the auxiliary heat to W2 jumped to W3/AUX.
— Connect the emergency heat to W1/E. See Fig. 18.
11
TZ-4 TOTALZONE® ZONE CONTROL PANEL
ZONE 2
ZONE 3
ZONE 4
ZONE LEDs
ON
Damper open or opening
35 F
OFF Damper closed or closing
40 F
PURGE
BOOT
OVERRIDE
45 F
Zone-
A-Lone
MOMENTARY PUSH BUTTONS
Boot – Clears microprocessor
Purge Overide – Bypass Purge Mode
DIP SWITCH S5
AZ1
O
AZ2
N
OC
1
2 3 4 5 6 7 8
OC
TABLE 2
#5 #6 #7
TIME
1 1 1
5 MIN
1 1 0
10 MIN
1 0 1
15 MIN
1 0 0
20 MIN
0 1 1
30 MIN
0 1 0
40 MIN
0 0 1
50 MIN
0 0 0
60 MIN
ZONE 4
2
2
Damper
Thermostat
W3/
W1/
W3/
W2
AUX
M6 M4 M1
C
R
E
Y1
G
O/B Y2
W2
AUX
L
L
1
W2
W3/
L
C
R
W1
Y1
G
O/B
Y2
W2
W3/
L
AUX
AUX
Zone 4 Thermostat
Power-closed
Spring-open
(Model ARD)
ON
EM
Heat
OFF
Occup
Unoccup
Add-A-Zone
Panel(s)
Remote
Zone-A-Lone
24VAC, 40VA
Transformer
PANEL
XFRM
R
R
C
C
T1
T2
DAMPER
XFRM
C R
Damper
24VAC, 40VA
M6 M4 M1
Transformer
(Required if
more than
four dampers)
M20520B
68-0259-1