Download Print this page

Floating/2-Position Run Mode; Limitation Of Rotation Stroke; Internal End Switches; Manual Adjustment - Honeywell CN05 Series Manual

Non-spring return direct-coupled damper actuators for floating and two-position control

Advertisement

CN05,CN10 SERIES DAMPER ACTUATORS FOR FLOATING/2-POSITON CONTROL

Floating/2-Position Run Mode

If the function selection switch has been set to one of the two
floating/2-position control settings—and if the actuator is wired
correspondingly (see Fig. 7, Fig. 8, and Fig. 9)—then as soon as
operating power is applied, the shaft adapter will run according to
the control signals applied.
Table 1 describes the behavior ("stops," rotates "CCW," or
rotates "CW") of the CN6105/CN6110 in dependence upon the
control signals (switch "open" or "24 Vac/dc") applied to terminals
3 and 4, the function selection switch setting, and the manner in
which the actuator is wired (either for floating mode: see Fig. 7;
or for 2-position mode: see Fig. 8).
Table 1. Behavior of CN6105/CN6110
wiring
control signal at
term 3
term 4
float.
open
open
open
24Vac/dc
24Vac/dc
open
2-pos.
24Vac/dc
open
24Vac/dc
24Vac/dc
Table 2 describes the behavior ("stops," rotates "CCW," or
rotates "CW") of the CN4605/CN4610 in dependence upon the
control signals (switch "open" or "230 Vac") applied to terminals 1
and 3 and the function selection switch setting: only one manner
of wiring is permitted (see Fig. 9).
Table 2. Behavior of CN4605/CN4610
control signal at
term 1
term 3
open
open
open
230 Vac
230 Vac
open
230 Vac
230 Vac

MANUAL ADJUSTMENT

IMPORTANT
To prevent equipment damage, before manual
adjustment, you must remove power or set the func-
tion selection switch to the "Service/Off" position.
After removing power or setting the function selection switch to
the "Service/Off" position, the gear train can be disengaged using
the declutch button, permitting the shaft adapter to be manually
rotated to any position.
switch setting
Dir
Service/ Off
Rev
stops
stops
stops
CCW
stops
CW
CW
stops
CCW
CW
stops
CCW
CCW
stops
CW
switch setting
Dir
Service/ Off
Rev
stops
stops
stops
stops
stops
stops
CW
stops
CCW
CCW
stops
CW

Limitation of Rotation Stroke

Two adjustable mechanical end limits are provided to limit the
angle of rotation as desired (see Fig. 3). The mechanical end
limits must be securely fastened in place.
Fig.3.
To ensure tight closing of the dampers, the shaft adapter has a
total rotation stroke of 95°.

INTERNAL END SWITCHES

The internal end switches "A" and "B" are changeover switches
which are activated when the shaft adapter moves past a position
of 5° and 85°, respectively (see also Table 5).
Fig.4.
Internal end switch triggering points