Switching The Control Panel Between The Supply And Inverter Units - ABB ACS800-17LC Hardware Manual

Drives (55 to 5200 kw)
Table of Contents

Advertisement

114

Switching the control panel between the supply and inverter units

The control panel is switched between the supply unit and inverter units as follows:
Step
Action
1.
To enter the Drive Selection Mode
Note: In local control mode, the inverter unit trips if
parameter 30.02 PANEL LOSS is set to FAULT. Refer to
the appropriate application program firmware manual.
2.
To scroll to ID number 2
3.
To verify the change to the supply unit and display the
warning or fault text
Step
Action
1.
To enter the Drive Section Mode
2.
To scroll to ID number 1
3.
To verify the change to the inverter unit
WARNING! The drive does not stop by pressing the control panel Stop key in remote
control mode.
Start-up
Changing control to the supply unit
Changing control to the inverter unit
Press...
Display (example)
ACS 800 0490_3LM
DRIVE
ASXR7xxx
ID-NUMBER 1
ISU 800 0490_3LM
IXXR7xxx
ID-NUMBER 2
2
-> 380.0 V
ACT
ISU 800 0490_3LM
*** FAULT ***
DC OVERVOLT
Press...
Display (example)
ISU 800 0490_3LM
DRIVE
IXXR7xxx
ID-NUMBER 2
ACS 800 0490_3LM
ASXR7xxx
ID-NUMBER 1
1 L
-> 0.0 rpm I
FREQ
ACT
CURRENT
POWER
(3210)
0.00 Hz
0.00 A
0.00 %