114
Switching the control panel between the supply and inverter units
The control panel is switched between the supply unit and inverter units as follows:
Step
Action
1.
To enter the Drive Selection Mode
Note: In local control mode, the inverter unit trips if
parameter 30.02 PANEL LOSS is set to FAULT. Refer to
the appropriate application program firmware manual.
2.
To scroll to ID number 2
3.
To verify the change to the supply unit and display the
warning or fault text
Step
Action
1.
To enter the Drive Section Mode
2.
To scroll to ID number 1
3.
To verify the change to the inverter unit
WARNING! The drive does not stop by pressing the control panel Stop key in remote
control mode.
Start-up
Changing control to the supply unit
Changing control to the inverter unit
Press...
Display (example)
ACS 800 0490_3LM
DRIVE
ASXR7xxx
ID-NUMBER 1
ISU 800 0490_3LM
IXXR7xxx
ID-NUMBER 2
2
-> 380.0 V
ACT
ISU 800 0490_3LM
*** FAULT ***
DC OVERVOLT
Press...
Display (example)
ISU 800 0490_3LM
DRIVE
IXXR7xxx
ID-NUMBER 2
ACS 800 0490_3LM
ASXR7xxx
ID-NUMBER 1
1 L
-> 0.0 rpm I
FREQ
ACT
CURRENT
POWER
(3210)
0.00 Hz
0.00 A
0.00 %