Economizer logic modules for ventilation control
Hide thumbs Also See for W6215 Series:

Advertisement

W6215, W7215, W7460 ECONOMIZER LOGIC MODULES
Outdoor Sensor Input (W7215B and W7460B only)
The OSI sensor can be any sensor that provides a 2-10 Vdc
output. Mount the sensor according to the manufacturer
specifications. If not available, use the following guidelines:
1. Mount sensor in an area with unobstructed air circulation
that is protected from rain, snow, and direct sunlight.
DISCHARGE
AIR SENSOR
2
C7046A
INDOOR
FAN
DISCHARGE
AIR
1
FOR DIFFERENTIAL ENTHALPY, THE TWO C7400
ENTHALPY SENSORS ARE CONNECTED TO THE
W6215/W7215/W7460 ECONOMIZER CONTROL—ONE
IS MOUNTED IN RETURN AIR, AND THE OTHER IS
MOUNTED IN OUTDOOR AIR. DIFFERENTIAL
ENTHALPY CONTROL PROVIDES GREATER
ENERGY SAVINGS THAN SINGLE ENTHALPY.
2
USE EITHER MIXED AIR SENSOR OR DISCHARGE
AIR SENSOR, NOT BOTH.
Fig. 3. Representative locations of connected Economizer system devices.
Wiring
CAUTION
Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment
circuitry.
Disconnect power supply before installation.
IMPORTANT
1. All wiring must comply with applicable local codes,
ordinances and regulations.
2. Refer to Fig. 6 through 25 for typical wiring diagrams.
3. Refer to Table 2 for a list of the wiring diagrams and
corresponding Figure numbers in this document.
4. All device inputs and outputs must be 24 Vac Class 2.
NOTE: All connections with label designation ending in 1
(examples: TR1, T1, P1, Q1, AQ1) are ac/dc
common connections.
63-2544—3
DIRECT
EXPANSION
COIL
W6215,
W7215,
OR
W7460
IMPORTANT
Ensure proper polarity of sensor connections.
Incorrect polarity negates the sensor signal.
2. Connect it to the OA and OA1 terminals of the W7215B,
or W7460B (see Wiring section for details).
3. Adjust the OSI potentiometer setpoint to correspond to
OSI sensor voltage output at the threshold.
SPACE
THERMOSTAT
2
C7150B
MIXED AIR
SENSOR
SERIES
62 OR 72
ACTUATOR
1
C7400
ENTHALPY
SENSOR
EXHAUST
FAN
RETURN AIR
Optional Applications
Remote Minimum Position Control
Remote control of outdoor air dampers is desirable when
requiring temporary additional ventilation. One potentiometer
controls the damper minimum position, another potentiometer
controls the damper maximum position. The addition of
S963B1128 Remote Potentiometers allows occupants to open
or close the dampers beyond minimum position for modified
ventilation. Connect the potentiometers as shown in Fig. 4.
IMPORTANT
The minimum position signal takes priority to the
maximum position signal. With the maximum set
below the minimum, the logic module signals the
actuator to maintain the minimum position.
Free Cool Timing
The Free Cool contacts close while the logic module operates
free cooling. Connecting a timer to these contacts allows
tracking of the free cooling usage time.
4
INDOOR
AIR
SENSOR
ENTHALPY
C7400
1
SENSOR
OUTDOOR
AIR
SENSOR
OUTDOOR
AIR
EXHAUST AIR
M11816